External sensor connection
The controller cooperates with the outdoor temperature sensor type CT6-P. Install the
sensor on the coldest wall of the building - usually the north wall in a covered place. The
sensor must not be exposed to direct sunlight or rain. Install the sensor at a height of at
least 2 m above the ground, away from windows, chimneys and other heat sources that
could interfere with temperature measurement (at least 1.5 m). Use a cable with a
conductor cross-section of at least 0.5 mm2 and a length of max. 25m. The polarity of the
wires is not important. Connect the other end of the cable to the controller terminals.
Screw the sensor to the wall using the mounting screws. You can access the screw holes by
unscrewing the sensor cover.
Connection of external sensor CT6-P.
Check of temperature sensors
Temperature sensors can be checked by measuring their resistance at a given
temperature. If you find larger differences between the measured resistance value and the
values in the following table, the sensor must be replaced.
CT4
Temp.
°C
Min.
Ω
Men. Ω Max.
Ω
0 802 815 828
10 874 886 898
20 950 961 972
25 990 1000 1010
30 1029 1040 1051
40 1108 1122 1136
50 1192 1209 1225
60 1278 1299 1319
70 1369 1392 1416
80 1462 1490 1518
90 1559 1591 1623
100 1659 1696 1733
45


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for ATTACK Pellet 30 Automatic Plus at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of ATTACK Pellet 30 Automatic Plus in the language / languages: English as an attachment in your email.

The manual is 0.97 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of ATTACK Pellet 30 Automatic Plus

ATTACK Pellet 30 Automatic Plus User Manual - German - 56 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info