53
EN
After pressing the „S” by displayed „EFFECT ADJ.“ is in the left upper corner displayed „OUTPUT 1
(kW)“. In the left bottom corner will be „O:16“ (i.e. the actual value of the actuator output in kW).
To change the actuator output, press the „+“ button, until the required value is displayed in the
right bottom corner, i.g. „N:18“. If you press „S“ now, this new value (18 kW) will be saved for the
output level 1. After this, the output level 2 is displayed („OUTPUT 2“) and it can be set to the
required value. If it will not be changed, press „S“ to save the value indicated on display, i.g.
„N:22“, i.e. the output level 2 (OUTPUT 2) will be 22 kW.
If you wish to let the display without saving the changes, press „ESC“.
Setting of ignition:
Here you can adjust the ration of fuel for ignition in %; this value
was automatically calculated adequately to the weight given in
the Feeder setting – amount.
By pressing the „S“ button, the „Ignition amount 1“ is displayed in the left upper corner. Changes
are made in %, the starting amount was pre–set to 170 g. If you increase this amount to 110%,
the starting amount will be changed to 187 g.
If the first trial of the burner ignition fails, the Ignition amount 2 is activated, which is pre–set
from production to 45 % from 170 g, i.e. 76,5 g.
Setting of time of the test blow–through
Time of the test blow–through defines the time, within which will
be the boiler and the chimney ventilated before beginning the
combustion (10 – 100 seconds).
For boilers, at which there is tough to achieve their draught, it is recommended to increase the
time of test blow–through. From production it is set to 15 sec.
Setting of the transition period:
Here you can select the duration since the first recognizing of the
fire up to the feeding of full amounts of pellets, adjusted by the
actuator output.
There are two parameters of the transition phase: the first is 14 kW and the second is 30 kW. The
time set by the first parameter determines, how long it will take to achieve 14 kW, time of the
second parameter determines time to achieve 30 kW since the fire is recognized. The lower the
required output is, the shorter is the period necessary to achieve it.
Setting of the fuel supply during the transition phase:
Here you can set the fuel amounts that are feeded during the
transition phase, since the fire is recognized until the burner
achieves the output of 14 kW.
Set the required amount to be feeded into the burner after the fire recognition. The supplied
amount will be gradually increased with every ration during the stated period. From production
it is set to 15% from the full ration for 14 kW.
IGNITION SETTING
ENTER < > EXIT
TEST BLOWING
ENTER < > EXIT
TRANS. PHASE
ENTER < > EXIT
TRANS. FEED.
ENTER < > EXIT
54


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for ATTACK DPX Combi Pellet at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of ATTACK DPX Combi Pellet in the language / languages: English as an attachment in your email.

The manual is 8.73 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info