810409
54
Zoom out
Zoom in
Previous page
1/96
Next page
EN
www.atmos.cz
54-EN
Operation and maintenance manual - EN
the output for the external conveyor from which pellets fall directly to the burner gets damaged,
the reserve will be switched off automatically. This function is convenient in cases when you
need to control another external conveyor that supplies (feeds) pellets from a larger distance to
a pellet bin at the boiler from which the main external conveyor draws pellets to supply them
directly to the burner. Caution - the other external conveyor must always be controlled with an
additional level sensor (level meter) that will maintain the level of pellets in the pellet bin at the
boiler. This is a similar function to S6 = 9, but with a higher degree of safety.
k) S6 = 11….. Reserve function for controlling boiler exhaust fan for DCxxSP(X), CxxSP, ACxxSP
boiler types when the function for automatic start after wood is burnt out is activated. This function
ensures that boiler exhaust fan is running only during wood burning after the wood is burnt out.
When the burner is run on pellets, the boiler exhaust fan remains switched off. This function is
used if you do not need or want to use the boiler exhaust fan while the burner is running. Install
the AD02 module under the instrument hood of the boiler and connect it electrically between the
boiler terminal board and the extraction fan, see the wiring diagram.
WARNING – this is not a standard setting for DCxxSP(X), CxxSP, ACxxSP boilers with
the function of automatic start.
(AUTOSTART – S34 = 1 or S34 = 2) after wood is burnt out (standard setting is S6 = 4).
l) S6 = 12…..Reserve function for direct control of pump in the boiler circuit from the burner
regulation (boiler terminal board). This function controls the pump in the boiler circuit without
using AD02 or AD03 modules. This is applicable only for boilers that do not allow heating with
wood (not even in emergency situations). E.g. D14P, P14, D21P, P21, D25P, P25, D80P, P80,
DxxPX, PXxx. Pump output must be switched to reserve R on the boiler terminal board and the
TK sensor must be installed before this function can be activated. After activation, S37, S38, S39,
S40 temperature parameters must be checked and configured.
m) S6 = 13…..Reserve function is the reverse output function for controlling the pump in
the boiler circuit from the burner regulation (output cable from boiler with a connector – white
inside) via AD02 or AD03 modules. This function controls the pump in the boiler circuit using
AD02 or AD03 modules ranged into a set with pump thermostat installed into the boiler panel.
This method of pump controlling can be used for any ATMOS pellet boiler, and is therefore
recommended. AD02 or AD03 modules must be inserted and connected under the boiler hood
and the TK sensor must be installed before this function can be activated. After activation, S37,
S38, S39, S40 temperature parameters must be checked and configured.
n) S6 = 14….. Reserve function for direct control of solar heating pump from the burner regulation
(boiler terminal board). This function control solar pump when automatic sensor switching function
is activated (S15=3), where the boiler is connected with accumulation tank equipped with solar
exchanger and collectors. The system requires TV, TK, TS and solar sensors to be connected to the
TSV solar panel. This function never uses AD02 or AD03 modules.
After activation, S26, S27, S28, S29, S30, S31, S32, S33 temperature parameters must be checked
and configured.
This function is specially designed for boilers: D14P, P14, D15P, P15, D20P, P20, D21P, P21,
D25P and P25
54


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Atmos A25 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Atmos A25 in the language / languages: English as an attachment in your email.

The manual is 16.33 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Atmos A25

Atmos A25 User Manual - German - 70 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info