Operation and maintenance manual - EN
• Parameter S2 - fan speed at the START… (1 %) - do not change
CAUTION - 1 % = 700 rpm. If S2 = 0, the fan is off at the start.
• Parameter S3 – Fan speed during normal RUN… (100 %)
In normal circumstances we do not recommend you to reduce the fan speed as it influences
cooling and cleaning of inner parts of the burner. Only use the air flap to set the air quantity.
• Parameter S4 – Fuel ignition control method …(1)
If:
a) S4 = 1…. Photocell sensing
• Parameter S6 – characterizes the first reserve R - additional output - function… (4)
The first reserve R is used mainly for controlling boiler exhaust fan (S6 = 4 )
CAUTION – In the standard setting when parameter S1 is set to 2, you can connect to
the reserve terminal
R, R2, R5 and R6
an appliance with the maximum current of 2.46 A
(approx. 566 VA).
In the setting when parameter S1 is set to 4, which means that at the start both the ignition
spirals are activated simultaneously, you can connect to the reserve terminal R, R2, R5 and
R6 an appliance with the maximum current of 0.29 A (approx. 67 VA).
If:
a) S6 = 1…. If any fault occurs in the burner and the burner is shut down, the reserve relay will
be closed and the reserve output will be energized. Thanks to this you can start a spare source
of energy for heating of the building as e.g. a gas, electric or oil boiler.
b) S6 = 2….. If any fault occurs in the burner and the burner is shut down, the reserve relay will
be opened and the reserve output will not be energized. Thanks to this a signal can be sent to
an electrically backed up AB01 ATMOS GSM module controller that will send information that
there is a system fault or the system is not energized. This is the opposite logic (to S6 = 1), which
means that during normal operation the reserve is energized.
c) S6 = 3…… The reserve function as the output function for the burner fan, when the reserve
output is closed, is energized always when the burner fan is running (fan mode only 100 % or
OFF). This function is applied if you want the boiler fan or extraction fan in the chimney to run
together with the burner fan. This function is designed for direct control of an fan directly from
the burner (e.g. DxxPX, PXxx).
d) S6 = 4…… The reserve function as the reversed function of the output for the burner fan,
when the reserve output is off, is not energized always when the burner fan is running. This
function is always activated if you connect the A25 burner with the AS25 set containing the
AD02 or AD03 module, which in this case controls the extraction fan of the boiler. Install the
52


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Atmos A25 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Atmos A25 in the language / languages: English as an attachment in your email.

The manual is 16.33 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Atmos A25

Atmos A25 User Manual - German - 70 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info