COMMISSIONING
Combustion checking procedure
The order of operations for this procedure must always be
respected.
Refer to Technical Bulletin 143 on Gas Safe Register website for
further information on combustion analysis of domestic boilers.
Operation 1 - Supply pressure check
Loosen the screw 1 and insert the pressure gauge connection
pipe into the pipe tap.
Switch the boiler on at maximum power.
To activate combustion test function:
- Press the mode selector to ensure the
icons displayed.
- Press & hold the reset button for 10 seconds. ‘
’ will
appear on the screen. Ensure the boiler is on max power by
pressing the button 2
.
The supply pressure should correspond to the value established
in relation to the type of gas ,for which the boiler is designed see
Table summarising changes.
Note:
The absolute minimum working pressure measured at the inlet
test nipple on the gas valve is 17.5 mbar.
Operation 2 - Preparing the measuring equipment
Connect the calibrated ue gas analyser to the left-hand
combustion outlet by unscrewing the screw and removing the
blanking cover.
Operation 3 - Adjusting the CO2 at maximum gas ow rate
(domestic hot water)
Draw off the domestic hot water at the maximum water ow rate
(if a combi).
Select the Test function by pressing the
RESET button for 10 seconds.
WARNING! When the cleaning function is activated, the
temperature of the water coming out of the boiler may be
more than 65°C.
On the display appear
and the icon
. The boiler is foced to the maximum
heating power.
Press the 2
button to forced the boiler at
the maximum DHW power. On the display
appear the icon
.
Wait 1 minute for the boiler to stabilise before
carrying out the combustion analyses.
Read the CO2 value (%) and compare it with the values given in
the table below
N.B.: VALUES WITH THE CASING CLOSED.
If the CO2 value (%) read differs from the values given in the
table, then adjust the gas valve following the instructions below,
otherwise move directly onto operation 4.
Adjusting the gas valve at maximum gas ow
Adjust the gas valve by turning setting screw 4 clockwise in
increments to reduce the CO2 level (a 1 turn adjusts the CO2
level by approximately 0.2%). Wait 1 minute after each change in
setting for the CO2 value to stabilise.
If the value measured corresponds to the value given in the
table, max adjustment is complete, otherwise start the setting
procedure again.
N.B. The Test function is automatically deactivated after 10
minutes or manually by briey pressing the RESET button.
Operation 4 - Checking the CO2 at
minimum gas ow
With the Test function active, press the 2
button to select the icom and
. The boiler is forced to the minimum power.
Wait 1 minute for the boiler to stabilise
before carrying out the combustion analyses.
If the
CO2 value (%) read differs by 0.5 % from the value found,
then adjust the gas valve following the instructions below,
otherwise move directly onto operation 5.
Adjusting the gas valve to minimum gas ow
Remove
cap and adjust screw 2 by turning anti-clockwise in
increments to reduce the CO2 level. Wait 1 minute after each
adjustment for the CO2 value to stabilise.
WARNING! this adjustment is sensitive: a rotation of a 1 turn
corresponds to 0.2% of CO2.
1 32 4
2
4
1
E-COMBI ONE
E-SYSTEM ONE
Gas CO
2
(%) MAX CO
2
(%) MIN
G20 8,7% ÷ 9,7% 8,4% ÷ 9,4%
G31 9,5% ÷ 10,5%
ATTENTION! CO
2
max – CO
2
min > 0,5%
1 32 4
4
35


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Ariston E-System One at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Ariston E-System One in the language / languages: English as an attachment in your email.

The manual is 11,88 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Ariston E-System One

Ariston E-System One User Manual - English - 12 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info