INSTALLATION
Gas Supply
The gas installation and tightness testing must be in accordance
with the requirements of BS6891. Ensure that the pipe size is
adequate for demand including other gas appliances on the same
supply.
Electrical Supply
The appliance requires an earthed 230V - 50 Hz supply and must
be in accordance with current I.E.E. regulations. It must also be
possible to be able to completely isolate the appliance electrically.
Connection should be via a 3 amp double pole fused isolating
switch with contact separation of at least 3mm on both poles.
Alternatively, a fused 3 amp, 3 pin plug and unswitched socket
may be used, provided it is not used in a room containing a bath or
shower, it. It should only supply the appliance.
Automatic by pass
Ariston recommend that an automatic by pass is installed a minimum
of 1.5 metres away from the boiler to ensure the minimum required
flow rate is achieved at all times. Additionally the design of the
system and its controls must ensure that an adequate temperature
diff erential is met, and should be such to prevent boiler cycling.
Feed and vent pipework
The feed and vent pipework from the boiler to the F & E (Feed &
Expansion) tank should be configured as shown in the fig. below.
Heating Circuit
Boiler
15mm (Min.)
Automatic By-Pass
Pump
2M
Minimum
150mm
Max.
500mm Minimum
Height
22mm (Min.) Vent Pipe
15mm (Min.) Cold Feed
Cylinder
R
F
Return
Flow
Return
Flow
Note:
The distance between the cold feed and the open vent pipe shall
be no more than 150mm.
The cold feed must be inverted as shown.
The open vent pipe must be a minimum of 22mm diameter.
The cold feed pipe must be a minimum of 15mm diameter.
The cold feed and open vent pipes must rise continuously and be
unrestricted.
• The minimum distance from the top of the boiler to the bottom
of the F & E tank shall be no less than 2m. Whilst the maximum
distance shall be not more than 27m.
The distance between the bottom of the F & E tank and the
highest point of the open vent must be no less than 500mm.
The flow and return pipes from the boiler must rise continuously
and be unrestricted.
The supply of water to the F & E tank should be taken from the
mains water supply via a suitable float operated valve. While the
supply from the F & E tank to the boiler/heating circuit (via the
cold feed) shall be unrestricted.
The F & E tank must be adequately supported and installed in
accordance with relevant Building Regulations.
Pump specification
The pump should be fitted on the flow pipe from the boiler and have
isolating valves each side. A variable duty pump should be set to
give a temperature differential of no greater than 20ºC.
Draining tap
A draining tap must be provided at all the lowest points of the
system which will allow the entire system to be drained. A drain tap
must also be installed on the flow and return pipes immediately
above the boiler to ensure complete draining of the primary flow
and return is possible.
Drain taps shall be to the current standard of BS 2879.
Sealed water systems
A sealed system kit is available from Ariston. Installation instructions
are supplied with the kit.
Pressure Loss Graphs through the boilers
mWH
l/h
0
100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
12-18 kW
12 kW
18 kW
821 l/h = 20 Δ @ 19.1 kW
555 l/h = 20 Δ @ 12.9 kW
1.3 mWH
2.65 mWH
24 kW
1118 l/h = 20 Δ @ 26.0 kW
3.7 mWH
10


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Ariston Clas HE R at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Ariston Clas HE R in the language / languages: English as an attachment in your email.

The manual is 16,14 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info