INSTALLATION
Codensate Discharge
The condensate discharge hose from the boiler must have
a continuous fall of 2.5
o
and must be inserted by at least
50mm into a suitable acid resistant pipe - e.g. plastic waste or
overflow pipe. The condensate discharge pipe must have a
minimum diameter of 22mm, must have a continuous fall and
preferably be installed and terminated to prevent freezing.
The discharge pipe must be terminated in a suitable position:
i) Connecting into an internal soil stack (at least 450mm above the
invert of the stack). A trap giving a water seal of at least 75mm
must be incorporated into the pipe run, there also must be an air
beak upstream of the trap.
ii) Connecting into the waste system of the building such as a
washing maching or sink trap. The connection must be upstream
of the washing machine/sink. If the connection is downstream
of the waste trap then an additional trap giving a minimum
water seal of 75mm and an air break must be incorporated in
the pipe run, as above.
iii) Terminating into a gully, below the grid level but above the
water level
iv) Into a soakaway
Note: If any condensate pipework is to be installed externally then
it should be kept to a minimum and be insulated with a waterproof
insulation and have a continuous fall. The total length of external
pipe used should not exceed 3 metres.
Some examples of the type of condensate terminations can be
found below.
1. Internal termination of condensate drainage pipe to internal stack.
2. External termination of condensate drainage pipe via internal
discharge branch (e.g. sink waste) and condensate siphon.
3. External termination of condensate drainage pipe via internal
discharge branch (e.g. sink waste - proprietary fitting).
4. External termination of condensate drainage pipe via condensate
siphon
Tundish
trap
Tundish
trap
Tundish
Tundish
External pipe length
max. 3 metres
(must be insulated)
Condensate Discharge
Push fit the flexible condensate pipe into the outlet spigot on the
appliance. Cut to length and locate outlet into a tundish
12


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Ariston Clas HE R at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Ariston Clas HE R in the language / languages: English as an attachment in your email.

The manual is 16,14 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info