2.4 Tools
TOOLS
A pressure gauge assembly
B pipe cutter
C recharge pipe
D electronic scale for refrigerant recharge
E dynamometric spanner
F clamp-shaped pipe vice
G xx mm hex key
H refrigerant canister
I vacuum pump
L HFC refrigerant leak detector
DYNAMOMETRIC SPANNER
2.5 Thickness of the copper pipes
NOMINAL DIAMETER
(inches)
EXTERNAL DIAMETER
(mm)
THICKNESS
(mm)
1/4 6.35 0.8
3/8 9.52 0.8
1/2 12.70 0.8
5/8 15.88 1.0
Split type air conditioning units operating with R410A refrigerant use a
three-way external unit valve with a pin valve.
2.6 How to connect the pipes
1. Only remove the pipe caps immediately prior to connection: under no
circumstances must you let dampness or dirt enter.
2. If a pipe is bent too many times, it becomes hard: do not bend it more
than 3 times in the same section. Unwind the pipe by unrolling it without
pulling.
3. The insulation around the copper pipes must be at least 6 mm thick.
2.7 Connections to the internal unit
1. Shape the connection pipes well following the outline.
2. Remove the end cap from the pipes of the internal unit (check that no
impurities have been left inside).
3. Insert the pipe union and position the fl ange at the end of the connection
pipe, following the instructions in the table (for copper piping):
ø
NOMINAL
ø
EXTERNAL
mm
THICKNESS
MEASUREMENT
A” mm
PIPE VICE
TRADITIONAL PIPE VICE
CLAMP-
SHAPED
BUTTERFLY
1/4 6.35 0.8 0-0.5 1.0-1.5 1.5-2.0
3/8 9.52 0.8 0-0.5 1.0-1.5 1.5-2.0
1/2 12.70 0.8 0-0.5 1.0-1.5 2.0- 2.5
5/8 15.88 0.8 0-0.5 1.0-1.5 2.0-2.5
41


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Ariston ALYS at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Ariston ALYS in the language / languages: English, Dutch, French, Italian, Portuguese, Spanish as an attachment in your email.

The manual is 2,95 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info