2. PIPING AND CONNECTIONS
1
4
3
2
WARNING:
- Only use piping specifi cally designed for ACR air conditioning
units.
- Protect all connection cables and pipes in order to prevent their
being damaged.
- Never use pipes with a thickness of under 0.8 mm.
- The appliance must be installed in full compliance with national
system regulations.
- During the installation process, the refrigeration system should
be connected fi rst, followed by the electricity supply. In the
event of replacement, proceed in the reverse order.
WARNING:
- Do not drink the condensation water (personal injury from poi-
soning).
- Position the condensation drain pipe in such a way as to allow
for the correct downward fl ow of water in dedicated areas, and
to prevent any inconvenience or damage to people, things, ani-
mals, plants and structures.
- Use manual tools and equipment that are suitable for the in-
tended purpose.
2.1 Connecting the refrigeration piping
The piping can be positioned in different directions as indicated by
numbers 1, 2, 3, 4 and 5 in the adjacent fi gure. When the pipes are po-
sitioned in directions 1, 3 or 5, the special groove marked on the side
of the internal unit should be cut using a suitable tool. Turn the pipes
in the direction of the hole in the wall, taking care not to constrict
them in any way, and tape the refrigeration system piping, condensa-
tion drain pipe and electrical wiring together with electric (insulating)
tape, keeping the condensation drain pipe at the bottom so that the
water can fl ow freely.
2.2 Draining the condensation from the internal unit
The proper draining of condensation from the internal unit is funda-
mental for a good installation.
1. Keep the condensation drain pipe (diameter 16,5 mm) at the bot-
tom of the hole in the wall.
2. Make sure the condensation drain pipe has a continuous gradient
of approximately 3 cm per metre.
3. Do not include any traps in the condensation discharge piping.
4. Do not immerse the free end of the condensation drain pipe in wa-
ter and do not leave it in the vicinity of places emanating unpleas-
ant odours.
5. When the installation is complete, before switching on the appli-
ance, make sure the condensation drain pipe works properly by
pouring some water into the condensation drip water tray situated
inside the internal unit.
2.3 Draining the condensation from the external unit
The condensation or water that forms in the external unit during op-
eration in heating mode can be removed via the drain pipe fi tting.
Installation: fasten the drain pipe fi tting (diameter 16 mm) to the hole
on the bottom of the unit, as illustrated in the adjacent diagram. Con-
nect the condensation drain pipe to the drain pipe fi tting and ensure
the other end of the pipe is ducted into a suitable drain.
PIPING INSULATION
CONDENSATION
DISCHARGE PIPE
REFRIGERATION
SYSTEM PIPING
REFRIGERATION
SYSTEM PIPING
SIGNAL CABLE
INSULATING SHEATH
YES NO NO
40


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Ariston ALYS at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Ariston ALYS in the language / languages: English, Dutch, French, Italian, Portuguese, Spanish as an attachment in your email.

The manual is 2,95 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info