1.3 Operating menu
E0: Factory default
If the system does not function as expected, even though the set points have
been adjusted, and the cause is impossible to locate, it is
recommended to note down the settings in the schedule. Thereafter the set point
must be adjusted to 1 and wait until the control returns to standard settings. Now
all the set points have been changed to the factory default. It is now possible to
start all over and adjust the set points.
Factory setting: 0
E2: T9 set temperature
This sensor is able to control the relay R9, which will be activated when the set-
point E2 is reached. The R9 relay can be used to control the three way damper
of the exhaust air. This three way damper can supply the living area with cool air,
if the room temperature reach the setpoint E2. For this function you will need a
separate sensor, which is not a within the standard delivering. The sensor shall
be connected to the control panel. For access to the control panel you have to
dismantle the top of the machine.
E2 can be set between 10-30°C
Factory setting: 21°C
E8: Disinfection function ON/OFF
By setting the point to 1, the electric cartridge will provide 65°C hot water, once a
week, in order to disinfect the tank (legionella protection function).
Factory setting: 0
E9: Operating in cold surroundings ON/OFF
If the setting is 0, the heat pump will run as long as there is a need of heat (=
exhaust air-operation).
Using the heat pump when taking the admission air from e.g. the cellar, there
is an option of making the compressor stop in case the room is getting to cold.
Instead, the electric heater will heat the water. The function is activated when the
value has been set to 1 (= circulating air-operation).
It is also possible to automatically let the electrical heater help heating the water
when the intake air temperature is below the temperature set in E10. The function
is activated when the value has been set to 2 (= fresh air operation). If the value
is 0, the function is not active.
Factory setting: 0
E10: Operating in cold surroundings
When activating the function menu E9, the temperature at which the compres-
sor will stop, or the heater will assist, may be set. The temperature is adjustable
between –10 and +10°C.
Factory setting: -5
E15: Hygrostat / stop unit
If the value is 0, the speed of the fans will change to 3 when the relative humidity
is above the preset value of the hygrostat. If the value is 1, the unit will stop when
the clips 25 and 26 are short-circuiting.
Factory setting: 0
E16: Min. airow
This value shows the minimum speed at which the fan is permitted to run when
operating. Notice that the cooling system may be overloaded,
resulting a drop out of the high-pressure switch, if the value has been set too
high. The value should not be chosen higher than necessary, in order to secure a
minimal airow through the cooling coil. Adjust this value between 0-100%.
Factory setting: 0
56


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for A.O. Smith AHD 290 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of A.O. Smith AHD 290 in the language / languages: English, German, Dutch, French as an attachment in your email.

The manual is 1,2 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info