743385
51
Zoom out
Zoom in
Previous page
1/56
Next page
CT100 Thermostat
Z Wave®
Anti-theft
The Anti-Theft Command Class disables a subset of supported/
controlled command classes in the thermostat if the thermostat is
being disconnected from and reconnected to a Z-Wave network.
(This thermostat supports version 2 of the Anti-Theft Command
Class.) This command class is typically used when installing a
thermostat in a public location, such as a hotel room or conference
center. The command class allows the user to lock the thermostat to
the actual Z-Wave network and to render it useless if it is removed
from the local network without being unlocked. Another application
would be to protect service-provider-owned products from leaving
the service providers network before they are paid for.
Disabled Commands With Engaged Anti-Theft protection
Basic Command Clock Command
Indicator Command Manufacturer Specifi c Command
Multilevel Sensor Command Thermostat Mode Command
Thermostat Operating State
Command Thermostat Fan Mode Command
Thermostat Fan State Command Thermostat Setpoint Command
Version Command Confi guration Command
Battery Command Association Command
Anti-theft Command
Multi Channel Command
(Only supported if a humidity sensor is
present.)
CT100 Thermostat
Z Wave®
Confi guration Parameters
This device supports the following Confi guration Parameters:
Name Set/Get Default Values
1 Temp Reporting Threshold Set/Get 2 0 to 4
2 HVAC Settings Get Only N/A see below
3 Utility Lock Enable/Disable Set Only 0 0 to 127
4 C- Wire/Battery Status Get Only N/A 0 or 1
5 Humidity Reporting Threshold Set/Get 2 0 to 3
6 Auxiliary/Emergency Set/Get 0 0 or 1
7 Thermostat Swing Temp Set/Get 2 1 to 8
8Thermostat Diff Temp Set/Get 4 4 to 12
9 Thermostat Recovery Mode Set/Get 2 1 or 2
10 Temp Reporting Filter Set/Get see below
11 Simple UI Mode Enable/Disable Set/Get 1 0 or 1
12 Multicast Enable/Disable Set/Get 0 0 or 1
1. Temperature Reporting Threshold (8-bit)
This value determines the reporting threshold when association
reporting is enabled. Unsupported values are ignored.
Value 01234
Treshhold Disabled Disabled 0.5°F 1.0°F 1.5°F
2. HVAC Settings (32-bit)
Byte 1 = HVAC Setup: Normal (0x01) or Heat Pump (0x02)
Byte 2 = Aux Setup (Gas (0x01) or Electric (0x02)) & Number of
Auxiliary Stages (Heat Pump)/Number of Heat Stages
(Normal)
Byte 3 = Number of Heat Pump Stages
Byte 4 = Number of Cool Stages
3. Utility Lock (8-bit)
If set to 0, the utility lock is disabled. All other values (1-255) enable
the utility lock.
51
51


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Z-Wave CT100 PLUS at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Z-Wave CT100 PLUS in the language / languages: English as an attachment in your email.

The manual is 1,69 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info