8-7
IM 1F5B2-01E
8. MAINTENANCE
8.3.3 Replacing the Sensor Assembly
(1) Removing the Sensor Assembly
NOTE
Sensor assemblies can be replaced only if your ULTRA YEWFLO is a flange model.
When removing the sensor assembly to replace it, follow the procedure described
below.
<1> Remove the amplifier unit according to the procedure in Subsection 8.3.2. (Refer
to Subsection 8.3.1 to remove an amplifier unit of ULTRA YEWFLO that has an
indicator/totalizer component.)
<2> Unplug the terminal pin at the tip of the sensor assembly from the terminal board.
<3> Loosen the clamp screw at the neck of the case.
<4> Remove the screws on the bracket that couples the sensor assembly with the body.
Remove the bracket together with the converter case.
<5> Remove the bracket that couples the case with the body.
<6> Remove the four screws on the plate that mounts the sensor assembly on the body.
<7> Remove the sensor assembly from the body, while exercising care to avoid forcibly
bending the assembly.
Bracket <5>
Bracket <4>
<6>Plate
Sensor assembly <7>
Terminal pin <2>
Figure 8.3-3 Removing the Sensor Assembly
59


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Yokogawa UYF200 Ultrasonic Vortex Flowmeter at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Yokogawa UYF200 Ultrasonic Vortex Flowmeter in the language / languages: English as an attachment in your email.

The manual is 0,93 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info