8.2.3 Trigger Level Adjustment (TLA) (Parameter H10)
TLA helps suppress the effects of external noise.
Parameter H10 (TLA) is adjusted to 0 as the default when ULTRA YEWFLO is
shipped from the factory.
ULTRA YEWFLO in principle is hardly affected by mechanical vibration. Make a
trigger level adjustment, however, if external noise is an issue or if ULTRA
YEWFLO gives a reading larger than the true value while the flowrate is zero.
Setting parameter H10 at a larger value (for example, a value from 0 to 2) heightens
the trigger level. This strategy will help reduce the effect of noise.
IMPORTANT
•Care must be taken when making a trigger level adjustment. If you set the parameter
for TLA at a value larger than necessary, the measurable lower limit of the flow
velocity rises to an unacceptable level, possibly impeding your measurement.
Before TLA Before TLA
High trigger level
Low trigger level
Waveform observed
across TP2 and COM
Waveform observed
across P and COM
Waveform observed across
TP2 and COM
Waveform observed across
P and COM
After TLA
High trigger level
Low trigger level
Waveform observed
across TP2 and COM
Waveform observed
across P and COM
Waveform observed
across TP2 and COM
Waveform observed
across P and COM
After TLA
Figure 8.2-3 Trigger Level Adjustment (at Lower Flowrates)
8.2.4 Loop Tests (Parameters F10 and F20)
You can have ULTRA YEWFLO provide either a 4-20 mA DC output of 0.0% to
110.0% (parameter F10: SET % MODE) or a pulse output of 0 to 6,000 Hz (param-
eter F20: SET F MODE) for your loop tests.
56


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Yokogawa UYF200 Ultrasonic Vortex Flowmeter at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Yokogawa UYF200 Ultrasonic Vortex Flowmeter in the language / languages: English as an attachment in your email.

The manual is 0,93 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info