5-6
IM 1F5B2-01E
5.5 Signal cable end finish procedure
For finishing signal cable end, following the procedure as below:
IMPORT ANT
The length of signal cable must be less than 20m.
(1) Remove the outer jacket, outer shield and inner
jacket as shown in the figure below.
10
65
Inner shield
Outer jacket
Inner
jacket
Outer shield
45
35
25
White
Red
55
(A)
(G)
(B)
(C)
Blue tubing
Black tubing
(A)
(G)
(B)
(C)
Heat shrinkable tubing
A
Tip
Label
7
Heat shrinkable tubing
Unit : mm
(2) Remove inner shield, intertwine two drain
wires, and cut each tip.
(3) Remove the wire insulation and twist each wire
as shown below.
(4) Insert insulation tubing over B and G until it
stops inside the shield. Cut the tubing off
leaving only 0.2 inch (5mm) of the inner shield
exposed. Remove 0.2 inch of insulation from
the tips of the two wires.
(5) Insert the heat shrinkable tubing as shown
below.
(6) As shown in the figure below, install the tip on
each wire and label of the sign which corre-
sponds to the each line.
(7) Heat all of shrinkable tube with a heat blower
or heat gun, and then shrink them.
33


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Yokogawa UYF200 Ultrasonic Vortex Flowmeter at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Yokogawa UYF200 Ultrasonic Vortex Flowmeter in the language / languages: English as an attachment in your email.

The manual is 0,93 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info