9.9. Help in the event of errors
ATTENTION: Opening the casing and manipulating the electrical connections is EXTREMELY DANGEROUS!
The mains fuse must be switched off before the front cover is removed.
WARNING: Due to external connections on the boiler control panel, individual cables or components on the
PYROGAS VARINO condensing unit can still be live even when the mains fuse is switched off.
9.9.1. No error code in the display
Unit is cold, the PYROGAS VARINO condensing unit is not in operation, no error code is shown in the display.
Status display: First figure = 0
Meaning: The condensing unit has no heat requirement and therefore no start command.
Possible cause: Ygnis heating controller (if present):
The heating controller is set to summer operation or switched off.
The operating instructions of the heating controller provide information on the
individual functions and applications of the heating controller.
External control with heating controller:
- the external heating controller should be checked.
- The heating curve may be set too low
Further procedure: Check cause, unit will start automatically when required.
Status display: First figure = 8
Meaning: Gas pressure monitor input is open
Possible cause: - The gas pressure is inadequate
- The gas cock is closed
- External safety gas valve is defect.
- The external mechanical ventilation does not work or builds up too little
pressure.
Further procedure: Check cause, unit will start automatically when required.
Status display: First figure = A
Meaning: The condensing unit is switched off
Possible cause: Fault lamp "external faults" lights up:
- The neutralisation set connected to the boiler control panel is overfull (if
present),
- external safety devices connected to the boiler control panel (e.g. water
shortage fuse, minimum/maximum pressure monitor, or external STB’s) have
been triggered.
Further procedure: The cause is not related to the condensing unit. After remedy of the external
cause the unit will start again without actuating the RESET button. A 5 minute
ventilation period will precede the start.
Possible cause: Fault lamp "external faults" does not light up:
- The burner switch on the control panel is switched OFF
- The maximum temperature set on the temperature monitor has been exceeded.
Further procedure: Check cause, unit will start automatically when required.
Possible cause: Fault lamp "sealing control" is lit (only when a sealing control has been optionally
added to the gas block):
- The gas supply is closed
- A leak has been found at one of the two gas valves of the gas block.
Further procedure: After the cause has been checked, the fault message must be acknowledged
with the "sealing control" release key. If the device still does not start after
acknowledgement has been made several times, the customer service must be
informed.
28


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Ygnis Varino at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Ygnis Varino in the language / languages: English as an attachment in your email.

The manual is 1,05 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Ygnis Varino

Ygnis Varino Usermanual and installation guide - German - 30 pages

Ygnis Varino Usermanual and installation guide - Dutch - 30 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info