CONDENSINOX - Installation, Use and Maintenance
1.5.3. Protecting steel and stainless steel boilers against corrosion
Corrosion can affect the iron components used in boilers and heating
systems, which is directly related to the presence of oxygen in the water
heater's water. Dissolved oxygen that enters the unit when it is being lled for
the rst time reacts with the equipment materials and quickly disappears. If
the oxygen is not renewed through signi cant contributions of water, the unit
might not experience any damage whatsoever.
However, it is important to follow the sizing rules and installation guidelines
in order to prevent oxygen from continuously owing into the heating water.
These rules include:
- Give preference to an expansion vessel with a membrane rather than an
open expansion vessel that allows direct passage.
- Ensure the pressure in the installation is greater than 1 bar when cold.
- Remove leaky (permeable to gas) components and replace with sealed
components.
If the guidelines above are followed, the unit's system water has the proper
characteristics to last a long time: 8.2 < pH < 9.5 with a dissolved oxygen
concentration of < 0.1 mg/l.
If there is a chance that oxygen could enter the unit, you must take additional
precautions. Adding an oxygen scavenger (e.g. sodium sulphite) is highly
recommended. We recommend directing any water treatment questions to
specialists, who can provide:
- The appropriate treatment based on the characteristics of the unit,
- A monitoring agreement with a guarantee as to the results.
In the case of an installation in which the water comes into contact with
a variety of materials, e.g. copper and aluminium, appropriate treatment is
recommended to ensure the long-term operation of the installation. In most
cases, this treatment will involve adding corrosion inhibitors in the form of
chemical solutions. We recommend contacting a water treatment specialist.
1.5.4. Unit monitoring
If the recommendations listed above (new installation or renovation) have
been followed, the unit monitoring is limited to:
- Checking the amount of make-up water ( ll water volume + make-up
water volume < 3 times the unit volume).
- Checking the pH (stable or rising slightly).
- Checking the water hardness (stable or falling slightly).
We recommend monitoring these parameters two to three times a year. Note
that monitoring the quantity of make-up water is vital to ensure the long-term
operation of the installation.
If any of these parameters deviates from the above recommendations, refer
to a water treatment specialist to correct the problem.
8


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Ygnis Condensinox at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Ygnis Condensinox in the language / languages: English as an attachment in your email.

The manual is 8,81 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Ygnis Condensinox

Ygnis Condensinox Installation Guide - Dutch - 74 pages

Ygnis Condensinox Installation Guide - Dutch - 43 pages

Ygnis Condensinox User Manual - Dutch - 18 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info