ALARMS
6 720 802 172 (2012/06) 23
Category: L.
Alarm lamp/buzzer: No.
Restart: The warning does not close anything but is registered in the
alarm log.
Check and clean the particle filter, if required.
Contact your installer if the warning remains after acknowledgement.
14.8.3 HIGH TEMPERATURE DIFFERENCE COLLECTOR CIRCUIT
E2X
Function: The warning is activated when the temperature difference
between collector circuit out and collector circuit in becomes too big.
Reset condition: The warning is deactivated on acknowledgement of
the warning display.
Category: L.
Alarm lamp/buzzer: No.
Restart: The warning does not close anything but is registered in the
alarm log.
Check and clean the particle filter, if required.
Contact your installer if the warning remains after acknowledgement.
14.8.4 THE HEAT PUMP IS NOW WORKING IN ANTI-FREEZE MODE
Function: Activated when the temperature in one of the circuits
becomes too low.
Reset condition: The temperature in the circuit is increased.
Category: L.
Alarm lamp/buzzer: No.
Restart: Automatic once the alarm cause has disappeared.
Contact your installer.
14.8.5 CHECK CONNECTION TO I/O BOARD X
Function: Depends on the board.
Reset condition: Communication with the board is re-established.
Category: M.
Alarm lamp/buzzer: No.
Restart: Acknowledgement is required.
Contact your installer.
14.8.6 CHECK CANBUS CABLE CONNECTION
Function: Communication with the controller has been interrupted. The
controller executes a new start if the alarm is still active after two hours.
If more than three new starts have been carried out within one hour, the
alarm Too high boot count I/O board BAS x (category A),
Chapter 14.7.7.
Category: M.
Alarm lamp/buzzer: No.
Restart: Acknowledgement is required.
Contact your installer if the warning recurs often.
14.9 INFORMATION LOG
The information log shows information from the heat pump.
14.9.1 HIGH FLOW TEMPERATURE E2X.T8
Function: The information is given if the temperature of the heating
medium is too high. The information can appear temporarily when high
room and hot water temperatures are set.
Reset condition: The information is deactivated when the temperature
falls to the permitted level.
14.9.2 TEMPORARY HEAT PUMP STOP E21.RLP
Function: Activated when the pressure in the refrigerant circuit of the
heat pump becomes too low. If the information appears several times
during a certain time period, the information transforms into a category
A alarm ( Chapter 14.7.2).
Reset condition: The pressure goes back to the permitted level.
14.9.3 TEMPORARY HEAT PUMP STOP E21.RHP
Function: Activated when the pressure in the refrigerant circuit
becomes too high. If the information appears several times during a
certain time period, the information transforms into a category A alarm
( Chapter 14.7.3).
Reset condition: The pressure goes back to the permitted level.
14.9.4 LOW TEMPERATURE COLLECTOR CIRCUIT IN E2X.T10
Function: The information is given if the temperature of the refrigerant
to the heat pump is too low. If the information appears several times
during a certain time period, the information transforms into a category
A alarm ( Chapter 14.7.5).
Reset condition: The temperature of the collector circuit exceeds the
lowest permitted temperature.
14.9.5 LOW TEMPERATURE COLLECTOR CIRCUIT OUT E2X.T11
Function: The information is given if the temperature of the refrigerant
from the heat pump is too low. If the information appears several times
during a certain time period, the information transforms into a category
A alarm ( Chapter 14.7.6).
Reset condition: The temperature of the collector circuit exceeds the
lowest permitted temperature.
14.9.6 HOT WATER PEAK FAILURE, NEW TRY WITHIN 24 HOURS
Function: The hot water has not come up at the right temperature. The
hot water peak is repeated at the same time on the next day.
Reset condition: The correct hot water peak temperature is reached.
14.9.7 TEMPORARY HEAT PUMP STOP DUE TO WORKING AREA
LIMITS
Function: The compressor stops until the hot gas temperature falls
below the set limit. The warning can occur when the heat pump works
close to the lowest permitted outdoor temperature.
Reset condition: The hot gas temperature is within the range of the
compressor.
14.9.8 TEMPORARY HOT WATER STOP DUE TO WORKING AREA
LIMITS
Function: Ongoing hot water operation is aborted and replaced with
heating operation. The warning can occur when the heat pump works
close to the lowest permitted outdoor temperature.
Reset condition: The hot gas temperature is within the range of the
compressor.
14.9.9 ADDITIONAL HEAT IS NOW WORKING AT ITS HIGHEST
TEMPERATURE
Function: The additional heat begins to be stepped down. The
information is activated in additional heat mode if the outgoing
temperature (T1 or T8) approaches the set maximum value. The
information is blocked during hot water peaks or extra hot water.
Reset condition: The information is deactivated when the temperature
falls.
14.9.10 TEMPORARY HOT WATER STOP E2X
Function: Ongoing DHW mode is temporarily interrupted; the system
changes over to heating mode.
Reset condition: DHW temperature drops a few degrees.
23


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Worcester Greenstore Ground Source at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Worcester Greenstore Ground Source in the language / languages: English as an attachment in your email.

The manual is 3.44 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info