ALARMS
6 720 802 172 (2012/06) 19
14.5 ALARM CATEGORIES
The alarms are divided into different categories depending on the type
and seriousness of the fault. Alarm category is displayed in the alarm
window and alarm log.
CATEGORIES A-H ARE ALARMS, CATEGORIES I-J ARE WARNINGS/INFORMATION, CATEGORIES K-M ARE WARNINGS, CATEGORY Z IS
INFORMATION.
[In] Temporary stop of compressor. The information may recur a
number of times during a certain time period; if there are more
during the period, a category A alarm is sounded.
[J] Temporary stop of compressor. The information may recur a
number of times during a certain time period; if there are more
during the period, a category A alarm is sounded.
[M] Used for board connection problems.
14.6 ALARM WINDOW
When an alarm/warning occurs, the display shows information about
what has happened. At the same time, information is saved in the alarm
log. The alarm symbol is displayed in the initial menu of the control panel
( Chapter 11.3).
Example of an alarm:
Fig. 31
14.7 ALARM FUNCTIONS
The different alarms that can occur are presented here, the alarm text is
indicated in the heading.
Most alarm texts contain a designation of the part of the heat pump that
has caused the alarm. Always indicate the whole alarm information when
you are in contact with the installer.
E21 refers to heat pump 1, E22 refers to heat pump 2.
E11 refers to circuit 1, E12 circuit 2, E13 circuit, 3, etc.
Txx refers to different temperature sensors.
14.7.1 HIGH HOT GAS TEMPERATURE E2X.T6
Function: Compressor stops. Activated when the temperature from the
compressor becomes too high. The alarm can occur in individual cases
under extreme service conditions.
Alarm timer starts: Yes.
Reset condition: The hot gas temperature drops to the permitted
temperature.
Category: A.
Alarm lamp/buzzer: Yes.
Restart: Acknowledgement is required.
Contact your installer if the alarm remains active for more than three
hours or recurs often.
14.7.2 TRIPPED LOW PRESSURE SWITCH E2X.RLP
Function: Compressor stops. Activated when the pressure in the
refrigerant circuit of the heat pump becomes too low.
Alarm timer starts: Yes.
Reset condition: The pressure goes back to the permitted level.
Category: A.
Alarm lamp/buzzer: Yes.
Restart: Acknowledgement is required.
Check the filter and clean if required (Chapter 16.3).
Contact your installer if the alarm remains after acknowledgement.
14.7.3 TRIPPED HIGH PRESSURE SWITCH E2X.RHP
Function: Compressor stops. Activated when the pressure in the
refrigerant circuit becomes too high.
Alarm timer starts: Yes.
Reset condition: The pressure goes back to the permitted level.
Category: A.
Alarm lamp/buzzer: Yes.
Restart: Acknowledgement is required.
Contact your installer if the alarm remains after acknowledgement.
14.7.4 LOW PRESSURE COLLECTOR CIRCUIT
Function: Compressor stops. Activated when the pressure in the
collector circuit becomes too low.
Alarm timer starts: Yes.
Reset conditon: The pressure goes back to the permitted level.
Category: A.
Alarm lamp/buzzer: Yes.
Restart: Acknowledgement is required.
Meaning A B C D E F G h In J K L M Z
Stops the compressor X XX XX X X
Stops additional heat XX X
Alarm lamp, alarm buzzer is activated X XX XXXXX
Alarm delay 5s 3s 15 min 1 min 5s 1s 1s 1s 5s 5s 2s 5s 0s 0s
Requires acknowledgement to restart X XX X X
Can be restarted before acknowledgement X X XXXX X
Menu display must be acknowledged X XX XXXXXXX
Placed in the information log X X X
Table 46 Alarm categories
6 720 643 415-15.1I
19


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Worcester Greenstore Ground Source at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Worcester Greenstore Ground Source in the language / languages: English as an attachment in your email.

The manual is 3.44 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info