Pre-Installation
Greenstar Danesmoor Utility 2022+ and Utility System 2022+ - 6 721 846 263 (2022/01) 23
4.9.2 Room sealed flue options
Fig. 27 Room sealed flue options
[A] Flue terminal
[B] Flue extension
[C] 90° bend
[D] 45° bend
[E] Vertical flue terminal
Figure 27 shows the components used and the maximum flue length (L)
for each flue configuration.
In all cases L is measured from the outside of the boiler casing.
To achieve the maximum flue length (L), a flue section will have to be
reduced in length.
Only the flue terminal or straight flue extensions can be reduced in
length by cutting.
The flue terminal end can be fitted from the inside or outside of the
building.
Calculating the flue length
Measure the total flue length required, noting that the maximum straight
flue length including the terminal is:
Horizontal 80/125mm Ø: 6000mm (excluding 120mm of terminal
extending outside the building)
Vertical 80/125mm Ø: 8000mm (measured from the boiler top panel).
Then reduce the total straight flue length for each extra flue bend
(excluding the vertical flue kit 90° elbow) by:
1000mm for 90°
500mm for 45°
Flue extension lengths
Horizontal & Vertical 80/125mm Ø: 1000mm overall length.
Effective length when engaged into sockets within the flue run is
950mm.
Flue terminal lengths
Horizontal 80/125mm Ø: 720mm
Vertical 80/125mm Ø: 1080mm + cage
* to outside wall.
L = 120 - 240mm L
A
L
L = 6000mm
125mm Ø
C
B
A
C
5 x
L = 8000mm
125mm Ø
L
B
E
L = 6000mm
125mm Ø
L
B
A
6 x
8 x
L
L = 6000mm
125mm Ø
C
B
A
5 x
L = 8000mm
L
D
D
B
E
125mm Ø
7 x
L = 8000mm
L
B
E
125mm Ø
7 x
L = 5000mm
125mm Ø
B
A
C L
5 x
6720808218-93.3Wo
L = 6000mm
125mm Ø
DD
B
A L
5 x
C
C
C
All horizontal sections must rise away from the boiler by
52mm per metre (3°) to allow the condensate to drain
back to the boiler.
23


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Worcester-Bosch Greenstar Danesmoor Utility Regular - Utility System at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Worcester-Bosch Greenstar Danesmoor Utility Regular - Utility System in the language / languages: English as an attachment in your email.

The manual is 14.85 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info