Commissioning
6720813171 (2016/05)42
Set the capacity to minimum (part load) according to the “Service
mode” menu ( table 11, page 34).
After the “Burner” LED ( fig. 86, [6]) has lit up wait for one minute
until the boiler is burning at part load.
Read the differential pressure during service mode. The differential
pressure (p
gas
- p
air
) must be –5 Pa (±5 Pa) (indication on the
pressure gauge: –10 to 0 Pa).
Fig. 88 Gas/air difference at low load
Enter the result in the commissioning log book ( section 10.5
“Commissioning record log book”, page 45).
If the gas/air-ratio is incorrect, it must be adjusted on the set screw
(Torx 40 H) [1]. The set screw is located behind the screw-on cover.
Fig. 89 Gas/air difference at low load
Press the “Chimney sweep” button ( fig. 86, [3]) until the dot
disappears from the display.
Switch off the heating system by pressing the mains switch of the
BC10 basic controller ( fig. 90, [1]).
Close the gas valve ( fig. 81, page 39).
Remove the measuring devices.
Tighten the screw in the burner pressure measuring nipple.
Slowly open the gas valve by pushing on the gas valve and turning it
¼ rotation in an anticlockwise direction ( fig. 79, page 39).
Switch on the heating system by pressing the mains switch of the
BC10 basic controller ( fig. 90, [1]).
Press and hold the “Chimney sweep” button ( fig. 90, [3])
(approximately 2 seconds), until the dot in the right-hand bottom
corner of the display ( fig. 90, [9]) appears. See also table 10,
“Flue gas test”, page 34.
After the “Burner” LED ( fig. 90, [6]) has lit up wait for one minute
until the boiler is burning at full load.
Press the “Chimney sweep” button ( fig. 90, [3]) to clear the
reading. See also table 10, “Flue gas test”, page 34.
Check that the boiler performance is still at the required value. See
table 13 “Settings”, page 36.
10.2.8 Carrying out a leakage test in operating conditions
Press and hold the “Chimney sweep” button [3] (approximately 2
seconds), until the dot in the right-hand bottom corner of the display
[9] appears. See also table 10, “Flue gas test”, page 34.
After the “Burner” LED [6] has lit up wait for one minute until the
boiler is burning at full load.
Use a foaming product to check all sealing locations in the total gas
circuit of the burner while the burner is active.
Press the “Chimney sweep” button [3] to clear the reading. See also
table 10, “Flue gas test”, page 34.
Fig. 90 BC10 basic controller
-15 -10 -5 0 5 (Pa)
-0.15 -0.10 -0.05 0.00 0.05 (mbar)
turn anticlockwise turn clockwise
wrong right wrong
6 720 648 726-088.1TD
6 720 648 726-089.1TD
1
DANGER: Danger of fatal accident from explosive
fumes.
Check the testing nipples used for gas tightness.
Only use approved leak detection products to locate
leaks.
WARNING:
Damage to the installation due to short circuits.
Cover any hazardous locations prior to locating the
leaks.
Do not spray the leak detection product on cable
runs, plugs or electrical wiring. Do not let it drip onto
them either.
DANGER: Danger of fatal accident from explosive
fumes.
Pipes and fittings may leak after commissioning
activities have been carried out.
Only use approved leak detection products to locate
leaks.
WARNING:
Damage to the installation due to short circuits.
Cover any hazardous locations prior to locating the
leaks.
Do not spray the leak detection product on cable
runs, plugs or electrical wiring. Do not let it drip onto
them either.
888
1
10
9
8
7
6
5432
1
6 720 648 726-069.1TD
11
42


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Worcester-Bosch GB162-80 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Worcester-Bosch GB162-80 in the language / languages: English as an attachment in your email.

The manual is 5,43 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Worcester-Bosch GB162-80

Worcester-Bosch GB162-80 Installation Guide - English - 12 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info