Installation
6720813171 (2016/05)22
8.3.3 Maximum Flue length (L)
The maximum pipe length (L) of the air supply and flue gas exhaust pipes
for the condensing gas system boilers is determined by the total
pressure loss of all components in the flue system.
Maximum length of horizontal or vertical extensions for 100/150 flue
system ( fig. 30 and fig. 31). For flue length see table 6.
Fig. 30 Vertical flue length
Fig. 31 Horizontal flue length
[A] Distance from centre of flue to inside rear wall
[B] Distance from centre wall bracket to centre of flue elbow
[L] Distance from centre of flue to outside wall
Take the flue pipe clearances into account when planning the layout of
the place of installation ( subsection 8.3.1: “Siting the flue terminal”
on page 20).
Maximum wall thickness without extensions is 415 mm. Maintain a
minimum side clearance of 8 mm ( fig. 28).
8.3.4 Additional flue parts
The additional flue parts listed can be ordered from your supplier.
Flue size 100/150 and 80/125
Weathering slates for 100/150 and 80/125
Flat roof, pitched roof.
8.3.5 Standard 100 mm flue systems
The standard concentric flue system provides for a max. horizontal
straight length ( table 6, subsection 8.3.4). Full instructions for
fitting this flue are in subsection 8.3.6: “Installation of the horizontal
flue” on page 23.
L
6 720 648 726-030.1TD
A
L
B
6 720 648 726-031.1TD
GB162 Maximum flue length [m]
concentric flue system
100/150 80/125
50 20 7,7
65 20 7.7
80 18
100 18
Table 6 Max. flue lengths, incl. wall/roofterminal in meters
GB162 Reduced flue length [m]
1)
1) For every bend or extension the max. flue length (L) has to be reduced.
concentric flue system
100/150
concentric flue system
80/125
bend extension bend extension
45° 90° 0.5m 1m 45° 90° 0.5m 1m
50 1.2 2.1 0.5 1.0 0.9 1.9 0.5 1.0
65 1.2 2.1 0.5 1.0 0.9 1.9 0.5 1.0
80 1.2 2.1 0.5 1.0 0.9 1.9 0.5 1.0
100 1.2 2.1 0.5 1.0 0.9 1.9 0.5 1.0
Table 7 Reduced flue lengths in meters
The total reduction length must never exceed the
maximum flue length.
Important: Any horizontal flue system fitted to a
condensing boiler must be inclined towards the
appliance at an angle of 52 mm per metre length to
prevent condensate dripping from the flue terminal.
This means that the clearance above the appliance must
be increased to match the duct length. See fig. 6 on
page 12.
22


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Worcester-Bosch GB162-80 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Worcester-Bosch GB162-80 in the language / languages: English as an attachment in your email.

The manual is 5,43 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Worcester-Bosch GB162-80

Worcester-Bosch GB162-80 Installation Guide - English - 12 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info