Bedienungsanleitung Steuerung S4_2006_09_25-neu.doc Page 31 / 83
© wodtke GmbH Tübingen. All rights reserved. Subject to change without notice. Month of issue xx/2007 Art. No. 950 281
Error code Cause of error
Desired
values How to correct error
TR =
Temperature at flue gas
fan
too low. Measuring point:
fan.
Sensor Pt 1000
Picture / case 1
Do not light! First empty
pot. See explanation on
the right.
Temperature sensor at flue gas fan
still too low after 21 minutes. Often
there are still unburnt pellets in the
burner pot.
Case 1: False start; burner pot filled
with pellets, no flame. temperature TR
is not reached
burner pot/appliance not cleaned
false start
negative pressure in installation
room (causes flow reversal in the
ignition system) false start (often
associated with flue gas escaping
from the appliance)
ignition cartridge defective false
start
TR 49 °C
TR Values
are sampled
continuously
starting 21
minutes after
the stove
start signal.
After restart
the first
sampling
again takes
place after
21 minutes.
Always empty and clean
burner pot before making a
new start. Note: Never empty
burner pot into fuel hopper –
danger of fire through
embers! Search for other
causes. Ensure sufficient
supply of combustion air.
Negative pressure in the
installation room, whether
caused by exhauster hood,
house ventilation system or
pneumatic conveyor systems,
is hazardous and must be
avoided. Observe country-
specific regulations and
separate technical information
included in the delivery. Then
do manual reset via I/O key.
Picture / case 2
Do not light! First empty
pot. See explanation on
the right.
Case 2: cause:
shutdown in mid
-
operation, because of too few pellets
in the fuel hopper or hopper has run
empty (only few pellets in the burner
pot)
Remedy in case 2: replenish
pellets, empty and clean
burner pot. Reset and start
anew.
Case 3:
no pellets in burner pot Case 3: cause: appliance has shut
down because ambient temperature is
too low + calorific output setting is too
low. Temperature remains below
desired TR during operation.
Remedy in case 3: increase
thermal output. Reset via I/O
key.
TP =
Temperature at pellet
chute too high
Measuring point: pellet
chute
Measuring sensor: Pt 1000
External error!
Possible causes include negative
pressure due to ventilation system or
exhauster hood or far too little
chimney draught with power failure
(fan).
TP < 200 °C
(only 6 kW
Airplus
appliances)
TP < 170 °C
(all other
appliances)
This is no hardware error!
Let appliance cool off until
TP falls below desired value.
Search for and correct
external cause. Only then do
manual reset via I/O key. See
above for more information on
negative pressure.
ST =
Temperature cutoff (STB)
has triggered.
Measuring point in
Waterplus appliances:
capillary sensor parallel to
FKY (measuring point for
TW) in heat exchanger
(mounted)
Measuring point in Airplus
appliances: capillary
sensor on heat reflector
plate of fuel hopper
Measuring sensor: STB
according to DIN 3440:
The
STB is an obligatory, self-
supporting safety comp-
onent with a control box of
its own that works indep-
endently of system control.
External error!
Temperature of boiler
or appliance too high. STB has
triggered because temperature is too
high (safety function). The cause is
almost always external, not due to the
appliance, since STB only triggers
when heat generated by the appliance
is not transmitted.
Possible causes:
Waterplus models: not properly
bled or operation without water or
with wrong connection to domestic
water system ( no / insufficient heat
transmission!!). Check external
hydraulics and external controls.
Airplus models: overheating.
Check convection inlets and
outlets. Reduce thermal output if
room temperature too high.
T
STB
95 °C
With
Waterplus
models the
current value
can be
determined
approx-
imately by
sampling TW
at menu level
1. Sampling
is not
possible with
Airplus
appliances.
This is no hardware error!
Let appliance cool off until
STB falls below desired
value. Search for and correct
external cause.
Only then release STB + do
manual reset via I/O key.
31


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Wodtke CW 21 Airplus S4 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Wodtke CW 21 Airplus S4 in the language / languages: English as an attachment in your email.

The manual is 3.18 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Wodtke CW 21 Airplus S4

Wodtke CW 21 Airplus S4 User Manual - German - 83 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info