WESTFIRE · WF36 WF37 WESTFIRE · WF36 WF37
11
UK
clear any soot falls which may have occurred due to the difference in combustion between the stove and the open fire.
If there is no existing chimney then either a prefabricated block chimney in accordance with Building Regulations
Approved Document J or a twin walled insulated stainless steel flue to BS 4543 can be used. These chimneys must
be fitted in accordance with the manufacturer’s instructions and Building Regulations.
A single wall metal fluepipe is suitable for connecting the stove to the chimney but is not suitable for using for the
complete chimney. The chimney and connecting fluepipe must have a minimum diameter of 150 mm and its
dimension should be not less than the size of the outlet socket of the stove.
Any bend in the chimney or connecting fluepipe should not exceed 45°. 90° bends should not be used.
If it is found that there is excessive draught in the chimney then either an adjustable flue damper or alternatively a
draught stabiliser should be fitted. The adjustable flue damper should not close off the flue entirely but should in its
closed position leave a minimum continuous opening free area of at least 20% of the total cross sectional area of
the flue or fluepipe.
Adequate provision e.g. easily accessible soot door or doors must be provided for sweeping the chimney and
connecting flue pipe.
Distance to Combustible materials
Combustible materials should not be located where the heat dissipating through the walls of fireplaces or flues could
ignite it. Therefore when installing the stove in the presence of combustible materials due account must be taken of
the guidance on the separation of combustible material given in Building Regulations Approved Document J and also
in these stove instructions.
UNIQ36 /
UNIQ36 Pedestal
UNIQ37 /
UNIQ37 Pedestal / UNIQ37 Large
Distance to combustible materials rear 175 mm 100 mm
Distance to combustible materials side 450 mm 600 mm
Distances to flammable materials/furnitures 1150 mm 825 mm
Hearth
The hearth should be able to accommodate the weight of the stove and its chimney if the chimney is not
independently supported.
The Westfire UNIQ36/ WF36 Pedestal and UNIQ37/ WF37 Pedestal wood stoves has been tested and is suitable to
be installed on a 12 mm non combustible plate such as Westfire 12 mm glass plates or 20 mm slate plates. Installa-
tion of all hearths should comply in size and construction so that it is in accordance with the provisions of the current
Building Regulations Approved Document J.
The clearance distances to combustible material beneath, surrounding or upon the hearth and walls adjacent to the
hearth should comply with the guidance on the separation of combustible material given in Building Regulations
Approved Document J and also in these stove instructions.
If the stove is to be installed on a wooden floor, it must be covered with a non-combustible material at least 12 mm
thick, in accordance with Building Regulations Approved Document J, to a distance of 30 cm in front of the stove and
15 cm to each side measuring from the door of the combustion chamber.
Combustion air supply
In order for the stove to perform efficiently and safely there should be an adequate air supply into the room in which
the stove is installed to provide combustion air. This is particularly necessary if the room is double-glazed or a flue
draught stabiliser is operating in the same room as the appliance. The provision of air supply to the stove must be in
accordance with current Building Regulations Approved Document J. An opening window is not appropriate for this
purpose. Air inlets must be positioned in such a way that they cannot be blocked. An air inlet may be a vent (the vent
must be open and the capacity of the vent sufficient when the stove is lit) or a fresh air system linked to the stove.
There are no European rules regarding the minimum distance to non-flammable walls, Westfire recommend leaving
a gap of at least 10 cm behind and to sides of stove.
11


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Westfire WF36 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Westfire WF36 in the language / languages: English, German, Dutch, Danish, French as an attachment in your email.

The manual is 3.24 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info