Outputs: pump:
Cold:
Heat:
3-point control:
5 A / 250 V relay (L, N, PE)
5 A / 250 V relay (L, N, PE)
5 A / 250 V relay (Free contact)
2 TRIACS => 75 W max.
"Maximum opening time 240 seconds; Suitable for actuators that have an
opening time below 240 Seconds”
Sensors: outside temperature:
supplied temperature:
return temperature:
CTN 10 K
at 25 °C (class II, IP55)
CTN 10 K at 25 °C (class I, IP68, no coupling)
CTN 10 K at 25 °C (class I, IP68, no supply)
Software version: _. (displayed when switched off – STOP mode).
9. TROUBLE-SHOOTING
X. TROUBLE
X.X
Possible reason Elimination
1. The display shows
1.1
at 13
Disconnected outside temperature sensor
Check whether the connection of sensor cable is correct.
Check the cable for damages.
Replace the cable or the sensor, if necessary.
1.2
at 5
Disconnected flow temperature sensor
Check whether the connection of sensor cable is correct.
Check the cable for damages.
Replace the cable or the sensor, if necessary..
2. Incorrect flow temperature
2.1
Incorrect flow setting temperature
The displayed calculated temperature is not in
accordance with the regulation curve.
Check if no offset are adjusted ( 6.1).
COMFORT and REDUCED temperature Offset.
2.2
Too high flow temperature due to incorrectly con-
nected valve drive (reverse action)
Check the connection of the valve drive ( 5.2).
2.3
Too low flow temperature due to incorrectly con-
nected valve drive (reverse action)
Check the connection of the valve drive ( 5.2).
2.4
Incorrect selected operation mode Select the correct mode of operation.
2.5
When ClimaticControl-HC operating in AUTO-
MATIC mode:
-
incorrect programming of built-in or user pro-
gram
-
incorrect setting of time / day of the week
-
Check the factory program or the user program settings
and pay attention to the correct setting of COMFORT and
REDUCED temperature periods of operation.
-
Check the setting of the time / day of the week.
3. The pumps or the valve drive does not work
3.1
Cable connections reversed. Check the electric connections ( 5.2).
3.2
Pump connected to temperature limiter.
-
Check the electric connection ( 5.2).
-
Check the maximum temperature setting of the TB.
-
Check the ambient temperature of the TB. If necessary,
change its position.
-
Check the TB operation. Replace it if necessary.
Remark:
Lock function
To prevent mistakes after installation, all critical parameters are not accessible any more after 4 hours power on. If
you want to modify these parameters, you must unplug and plug in controller. No settings are lost when unplug-
ging, or after a power failure.
After 4 hours you can still change all the other parameters to optimize your system.
25


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Watts Climatic Control Heating and Cooling at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Watts Climatic Control Heating and Cooling in the language / languages: English as an attachment in your email.

The manual is 2.88 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info