If PE = No Conventional operation of the free
contact "Heating output" (See Chap 5.3)
If PE = Yes See below explanations on “PE t”
-------------
PE t
(Efficiency Point
temperature
setpoint)
15
Setting the desired PE outdoor temperature.
If PE = Yes
• If the outdoor temperature is lower than the
Efficiency Point temperature setpoint and if a
heating request occurs, then the free contact of
the “heating output” will be closed to control an
auxiliary heat generator.
• If the outdoor temperature is higher than the
Efficiency Point temperature setpoint, and if a
heating request occurs, then the free contact of
the “heating output” will remain opened, f
orbidding
to switch on a backup heat generator.
-7°C
-20°C to
+ 15.0°C
16
Temperature indication in °C or °F °C
°F
17
Time indication mode
24 hours or 12 hours
24H
12H Am/Pm
18
Side
-
track protection
YES (ac-
tive)
NO (inactive)
When YES is selected the pump and the auxiliary actuator are activated at midday 12 hrs, if they
haven’t been active for a period of 24 hours. (12h00: Pump ON 1min, 12h01: Open actuator 2min,
12:03: Close actuator 2min)
The following parameter “Pumpis only used when no RF thermostats are installed and if no inputs (In1 & In2)
are used for connecting box (C_b) and aquastat (Aqu) function.
_ _ _ PUMP
19
Pump delay time:
Time duration to switch off the pump
after the stop demand from the
wired thermostat or after complete
close of the 3 way mixing valve.
This function is also interesting to
avoid permanent ON/OFF cycle of
the pump when “PWM” thermostat is
installed.
030
For best use
the duration
should be =>
2xPWM cycle
of the thermo-
stat
001 to 060,
and above “- - -“
= infinite delay, the
pump will be ON
all the time
20
Manual mode (or test function) for valve drive respectively 2/3
-
way valve
By pressing the (+) key the valve drive opens. The display shows “OPEN“ and .
By pressing the (–) key the valve drive closes. The display shows “CLOSE“ and ▼
By pressing the (◄) or (►) key current position of the valve drive is kept. Displays “STOP“
There is a actuator security anti-short delay: when switching from “OPEN“ to “CLOSE“
or “CLOSE“ to “OPEN“, the actuator will be stopped during 15s
Floor / screed preheating
program.
0 PrH
7 PrH
_ _ _ PrH
21
The program is started by selecting „7 dry“ and runs automatically.
For a period of 3 days the flow temperature is kept at 25 °C (days 7, 6, 5). For next 4 days the flow
temperature is maintained at its preset maximum value (days 4, 3, 2, 1).
The number of the days until the end of the heating program is displayed.
Floor / screed dehumidifi-
cation program
0 drY
Default value after
“ON”
=> 13 Days
7 to 60 days
22
The program is started by selecting the desired numbers of days and runs automatically.
Example: 13 days selected: (3days rise + 7days at Hi + 3days decrease)
For a period of 3 days the flow temperature will be increased up to the “Hi” value, then the tempera-
ture will be kept at the “Hi” value during 7 days. For the last 3 days the temperature will be decreased
up to the “Lo value.
Example2: 7 days selected: (3days rise + 1day at Hi + 3days decrease)
The number of the days left until the end of the fllor dehumidification program is displayed.
23


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Watts Climatic Control Heating and Cooling at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Watts Climatic Control Heating and Cooling in the language / languages: English as an attachment in your email.

The manual is 2.88 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info