Connecting to a flue of less than 4 m is not permitted by law.
As the chimney stack draught depends on a number factors, a side vent device can be
inserted at least 40 cm above the base to avoid overloading the fire and to avoid soot build
up. Side air devices can only be introduced into rooms where burning stoves are installed.
If there are a number of fire points in different rooms with a common chimney stack then
they are not permitted.
In addition to the points listed here, notice should be taken of DIN EN 13384, DIN
18160, EN 1856-2 and EN 15287.
The necessary combustion air can only be fed to the stove and the flue gases removed
through the chimney if an air exchange of at least 0.8 times per hour is guaranteed (doors,
windows, air duct).
Before connecting the stove seek advice from a chimney sweep.
2.3 The heating stove for open and closed systems
Heating stove model K157/K158 is only allowed to operate with heat sink in closed sys-
tems according to EN 12828, EN 12831 and EN 12897. If it is connected to an open sys-
tem then our guarantee for corrosion damage becomes invalid.
Heating stove model K157/K158, is suitable for open systems if a heat exchanger for the
heat sink is incorporated.
Further directions on central heating units are given in section 4.
Heating stoves for solid fuel can only be operated in closed systems with a flow independ-
ent heat sink with the safety valve mounted above the stove set at 2.5 bar.
The heat sink has to work in conjunction with the heat exchanger with large fires and low
heat loss of heating and domestic water which does not exceed the permissible highest
value of pressure in the heating pocket. The safety valve must therefore be checked regu-
larly. This is done by depressing the red button for a short time. Water must pass through
the valve while this is happening.
ATTENTION
The stove may only be heated up (even in testing) if:
- it is connected to a central heating system completely filled with water and
- The functioning of the thermal safety valve and the safety valve have been es-
tablished and inspected, if it is connected to a closed system.
2.4 Spacer connection and accessories
If the stove is to be integrated in a fitted kitchen, then the interface to a floor mounted cup-
board with a counter has to have a spacer connection which can be supplied by the fac-
tory. The available spacer connections are tested to EN with the stove and comply with
building regulation requirements relating to fire protection.
45


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Wamsler K158 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Wamsler K158 in the language / languages: English, German, French, Italian as an attachment in your email.

The manual is 2.07 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info