Up to a static height of 10 m, the capacity pressure expansion vessel is dependent on the
water capacity of the system as follows:
Water content Vessel size
Litre Litre
up to 111 12
112 - 167 18
168 - 231 25
232 - 324 35
325 - 463 50
464 - 741 80
There should no manually operable shut off valves installed between the expansion vessel
and the stove.
A ventilation section at least 0.5 m above the highest circulation point in closed systems
with a diameter of at least 1 should be arranged and a ventilation valve provided at the
upper end.
In gravity systems the rise and fall of horizontal pipes should be at least 0.5 cm/m.
Radiators with more than 25 ribs or plate heat exchangers over 1.5 m long should be di-
agonally connected to the flow and return pipes.
Where there is a lower distribution ventilating valve it must be provided on each radiator.
The radiators should not be inclined towards the ventilation. As radiators are usually at the
same level on the floor where the stove is installed, these radiators should all be connected
to a circulating pump as matter of course.
If however a pure gravity plant has to be executed without pumps, then the centre of the
radiator should not be lower than the centre of the boiler.
In the simplest installation case, the circulation pump is connected to the mains by a switch
and runs continuously during the heating period, while the water capacity of the stove is
regulated by an integrated temperature controller.
The pumps can however also be controlled from a maximum-thermostat in the domestic
water boiler, to ensure a minimum temperature for the domestic hot water.
It is also possible to switch the circulating pumps through a room thermostat. In this case
however the gravity circulating domestic water boiler should not have a capacity of less
than 260 l, if there are no other radiators on gravity circulation are connected.
Independently of the control types described above, the heating circulation and/or boiler
loading pump should primarily be controlled through a thermostat with a fixed switch on
temperature of between 50 and 55 °C, situated immediately at the stove's return flow con-
nection following an adjustable bypass close to the stove between the flow and return
lines, to avoid a low temperature operation of the stove boiler.
In the installation unit which can be supplied as an accessory there is a thermal boiler
monitor integrated as a continuous regulating valve. The pump controls mentioned above
are then not needed.
50


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Wamsler K148F at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Wamsler K148F in the language / languages: English, German, French, Italian as an attachment in your email.

The manual is 3.9 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info