32 D-307500 PowerMaster 360 Installer's Guide
Option
Configuration Instructions
Notes:
1. In some PowerMaster-360 variants, this menu is displayed in the Operation Mode only (see
section 4.14).
2. Since the Soak Test zone does not report an alarm event to the Monitoring Station, the
PowerMaster-360 will not send a cancel alarm message to the Monitoring Station even if
disarmed within the Cancel Alarm period.
39:ALARM RESET
Previously known as
RESET OPTION
The PowerMaster-360 provides you with the following configurable options for resetting the
alarm condition and rearming the system:
By the user as usual - by user (default). By the engineer (installer) by entering and exiting the
Installer Mode, by entering and exiting the Event Log using the Installer Code or by accessing
the system remotely via the PowerManage server using the Installer Code (by engineer). For
accessing the system via the PowerManage server, see the PowerManage User's Guide.
Note: This feature is not applicable in the USA.
40:ABORT FIRE T.
Select the length of time allowed by the system to abort a Fire alarm. The PowerMaster-360 is
able to provide an abort interval that starts upon detection of a Fire event. During this interval, the
buzzer sounds a warning but the siren remains inactive and the alarm is not reported. If the user
disarms the system within the allowed abort interval, the alarm is aborted.
Options: in 00 (default)/30/60/90 seconds
4.5.5 Configuring siren functionality
The following table provides you with a detailed description of each option and its configuration settings. To select an
option and change its configuration – refer to section 4.5.1.
Option
Configuration Instructions
44:SIREN TIME
Previously known as
BELL TIME
Define the period of time the sirens will sound upon alarm.
Options: 1 minute/90 seconds/3/4 minutes (default)/8/10/15/20 minute(s).
Notes:
1. To comply with EN requirements, the Siren Time must not exceed 15 minutes.
2. For Canada, the Siren Time must be set to 8 minutes.
45:STROBE TIME
Define the length of time the strobe light will flash upon alarm.
Options: 5/10/20 (default)/40/60 minutes.
4.5.6 Configuring audible and visual user interface
The following table provides you with a detailed description of each option and its configuration settings. To select an
option and change its configuration – refer to section 4.5.1.
Option
Configuration Instructions
53:MEMORY PROMPT
Define whether or not the user will receive Memory indication on the Virtual Keypad that an alarm
has been activated. By pressing the button in standby mode, you can view details of
the alarm memory.
Options: ON (default) and OFF.
54:LOW-BAT ACK
You can activate or deactivate the Low Battery Acknowledge requirement from the user whose
keyfob's battery is low. For further information, see PowerMaster-360 User's Guide Chapter 6.
Options: OFF (default) – acknowledge not needed; ON – acknowledge required.
56:SCREEN SAVER
With Partition
disabled
The Screen Saver option (when activated) replaces the status display on the virtual keypad
with PowerMaster-360 display if no key is pressed during more than 30 seconds.
You can activate the Screen Saver and determine whether the status display will resume
following any key press (refresh by Key) or by entering a code (refresh by Code). If refresh
by Key is selected, the first pressing of any key (except Fire and Emergency) will produce the
status display and the second press will perform the key function. For further information, see
the User's Guide, Chapter 1, Screen Saver Mode.
Options: OFF (default); refresh by Code and refresh by Key.
32


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Visonic Powermaster-360 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Visonic Powermaster-360 in the language / languages: English as an attachment in your email.

The manual is 2.8 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info