The MultiPlus is provided with a ground relay (relay H, see appendix B) that automatically connects the Neutral output to the
chassis if no external AC supply is available. If an external AC supply is provided, the ground relay H will open before the input
safety relay closes. This ensures the correct operation of an earth leakage circuit breaker that is connected to the output.
In a fixed installation, uninterruptable grounding can be secured by means of the grounding wire of the AC input. Otherwise the
casing must be grounded.
In a mobile installation, interrupting the shore connection will simultaneously disconnect the grounding connection. In that case,
the casing must be connected to the chassis (of the vehicle) or to the hull or grounding plate (of the boat).
In case of a boat, direct connection to the shore ground is not recommended because of potential galvanic corrosion. The
solution to this is using an isolation transformer.
The mains input & output terminal connector can be found on the bottom of the MultiPlus, see appendix A. The shore or mains
cable must be connected to the connector with a three-wire cable. Use a three-wire cable with a flexible core and a cross section
of at least 6 mm². Recommended torque: 1,6 Nm
Procedure (see appendix A) Do not invert neutral and phase when connecting the AC.
The inverter does incorporate a mains frequency isolating transformer. This precludes the possibility of DC current at any AC port.
Therefore type A RCD’s can be used.
AC-in
The AC input cable can be connected to the terminal block ‘AC–in’.
From right to left: “N” (neutral), “PE” (earth) and “L” (phase)
The AC input must be protected by a fuse or magnetic circuit breaker rated at 32A, and cable cross-section must be
sized accordingly. If the input AC supply is rated at a lower value, the fuse or magnetic circuit breaker should be down sized
accordingly.
AC-out
The AC output cable can be connected directly to the terminal block ‘AC-out’.
From left to right: “N” (neutral), “PE” (earth) and “L” (phase)
With its PowerAssist feature the MultiPlus can add up to 2kVA (that is 2000 / 230 = 9A) to the output during periods of peak
power requirement. Together with a maximum input current of 32A this means that the output can supply up to 32 + 9 = 41 A.
An earth leakage circuit breaker and a fuse or circuit breaker rated to support the expected load must be included in series with
the output, and cable cross-section must be sized accordingly.
4.4. Optional Connections
A number of optional connections are possible:
Undo the four screws at the front of the enclosure and remove the front panel.
4.4.1. Second Battery
The Multi has a connection (+) for charging a starter battery. For connection see appendix A.
Trickle charge output is protected by automatic overcurrent & overload protection (trip current 1A Imax= 5,5A)
4.4.2. Temperature Sensor
The temperature sensor supplied with the product may be used for temperature-compensated charging. The sensor is insulated
and must be mounted on the battery minus pole. Default output voltages for Float and Absorption are at 25°C. In adjust mode
temperature compensation is disabled.
4.4.3. Remote Control
The product can be remotely controlled in two ways:
With an external on/off switch (Remove Link “Remote Switch connector H”)
With a Multi Control Panel
Please see section 5.4 for appropriate DIP switch settings.
4.4.4. Programmable relay
The MultiPlus is equipped with a multi-functional relay that by default is programmed as an alarm relay. The relay can be
programmed for all kinds of other applications however, for example to start a generator (VEConfigure software needed).
4.4.5. Parallel Connection (see appendix C)
The MultiPlus can be connected in parallel with several identical devices. To this end, a connection is established between the
devices by means of standard RJ45 UTP cables. The system (one or more MultiPlus units plus optional control panel) will require
subsequent configuration (see Section 5).
MultiPlus 2kVA 230V
Page 7 Installation
9


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Victron MultiPlus 12 2000 80-32 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Victron MultiPlus 12 2000 80-32 in the language / languages: English as an attachment in your email.

The manual is 1.31 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info