Input voltage range
Voltage range accepted. The product synchronises within this range with the AC input. The output voltage is then equal
to the input voltage.
Adjustability:
Lower limit: 180 230V
Upper limit: 230 270V
Note : the standard lower limit setting of 180V is intended for connection to a weak mains supply, or to a generator with
unstable AC output. This setting may result in a system shut down when connected to a 'brushless, self excited,
externally voltage regulated, synchronous AC generator' (synchronous AVR generator). Most generators rated at 10kVA
or more are synchronous AVR generators. The shut down is initiated when the generator is stopped and revs down while
the AVR simultaneously 'tries' to keep the output voltage of the generator at 230V.
The solution is to increase the lower limit setting to 210VAC (the output of AVR generators is generally very stable), or to
disconnect the product from the generator when a generator stop signal is given (with help of an AC contactor installed in
series with the generator).
Inverter voltage
Output voltage in battery operation.
Adjustability: 210 245V
Stand-alone / parallel operation / 2-3 phase setting
Using multiple devices, it is possible to:
increase total inverter power (several devices in parallel)
create a split-phase system with a separate autotransformer: see VE autotransformer datasheet and manual
create a 3-phase system.
The standard product settings are for a single device in stand alone operation.
AES (Automatic Economy Switch)
If this setting is turned 'on', the power consumption in no-load operation and with low loads is decreased by approx. 20%,
by slightly 'narrowing' the sinusoidal voltage. Applicable in stand-alone configuration only.
Search Mode
Instead of the AES mode, the search mode can also be chosen. If search mode is 'on', the power consumption in no-
load operation is decreased by approx. 70%. In this mode the product, when operating in inverter mode, is switched off in
case of no load or very low load, and switches on every two seconds for a short period. If the output current exceeds a
set level, the inverter will continue to operate. If not, the inverter will shut down again.
The Search Mode 'shut down' and 'remain on' load levels can be set with VEConfigure.
The default settings are:
Action
Shut down
Turn on
Ground relay (see appendix B)
With this relay, the neutral conductor of the AC output is grounded to the chassis when the back feed safety relays are
open. This ensures the correct operation of earth leakage circuit breakers in the output. If required an external ground
relay can be connected (for a split-phase system with a separate autotransformer). See appendix A.
Battery charge algorithm
The standard setting is 'Four-stage adaptive with BatterySafe mode'.
This is the recommended charge algorithm for lead acid batteries. See the help files in the software configuration
programs for other features.
Battery type
The standard setting is the most suitable for Victron Gel Deep Discharge, Gel Exide A200, and tubular plate stationary
batteries (OPzS). This setting can also be used for many other batteries: e.g. Victron AGM Deep Discharge and other
AGM batteries, and many types of flat-plate flooded batteries.
With VEConfigure the charge algorithm can be adjusted to charge any battery type (Nickel Cadmium batteries, Lithium-
ion batteries)
14


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Victron EasySolar-II 48 3000 35-32 MPPT 250 70 GX at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Victron EasySolar-II 48 3000 35-32 MPPT 250 70 GX in the language / languages: English, German, Dutch, French, Italian, Swedish, Spanish as an attachment in your email.

The manual is 2.84 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info