8.5.3 Programmable analog/digital input/output ports
The product is equipped with 2 analog/digital input/output ports.
These ports can be used for several purposes. One application is communication with the BMS of a lithium-ion battery.
8.5.4 Voltage sense (connection terminal J, see Appendix A)
For compensating possible cable losses during charging, two sense wires can be connected with which the voltage
directly on the battery or on the positive and negative distribution points can be measured. Use wire with a cross-section
of 0,75mm².
During battery charging, the inverter/charger will compensate the voltage drop over the DC cables up to a maximum of 1
Volt (i.e. 1V over the positive connection and 1V over the negative connection). If the voltage drop threatens to become
larger than 1V, the charging current is limited in such a way that the voltage drop remains limited to 1V.
8.5.5 Temperature sensor (connection terminal J, see Appendix A)
For temperature-compensated charging, the temperature sensor (supplied with the inverter/charger) can be connected.
The sensor is isolated and must be fitted to the negative terminal of the battery.
8.5.6 Parallel Connection
It is required to use identical units for three phase and parallel systems. In this case, as only one GX device is allowed
per system, if you wish to parallel and/or three phase with this product, you must find the same model MultiPlus-II to pair.
To assist with finding identical units, consider instead using MultiPlus-II for parallel and three phase systems, and an
external GX device.
Up to six units can be connected in parallel. When connecting this product with MultiPlus-II in a parallel system, the
following requirements must be met:
WARNING
It is essential the negative battery terminal between the units is always connected. A fuse or circuit breaker is
not allowed on the negative.
All units must be connected to the same battery.
A maximum of six units connected in parallel.
The devices must be identical (aside from GX part) and have the same firmware.
The DC connection cables to the devices must be of equal length and cross-section.
If a positive and a negative DC distribution point is used, the cross-section of the connection between the
batteries and the DC distribution point must at least equal the sum of the required cross-sections of the
connections between the distribution point and the units.
Always interconnect the negative battery cables before placing the UTP cables.
Place the units close to each other, but allow at least 10cm for ventilation purposes under, above and beside
the units.
UTP cables must be connected directly from one unit to the other (and to the remote panel). Connection or
splitter boxes are not permitted.
Only one remote control means (panel or switch) can be connected to the system. That means only one GX.
8.5.7 Three-phase operation
The product can also be used in 3-phase wye (Y) configuration. To this end, a connection between the devices is made
by means of standard RJ45 UTP cables (the same as for parallel operation). The system will require subsequent
configuration.
Pre-requisites: see Section Voltage Sense
1. Note: the product is not suitable for 3-phase delta (Δ) configuration.
2. When the AS4777.2 grid code has been selected in VEConfigure, only 2 units in parallel per phase are allowed
in a three phase system.
For full details on parallel and three-phase configuration always discuss with your Victron distributor first and please see
this specific manual: https://www.victronenergy.com/live/ve.bus:manual_parallel_and_three_phase_systems
8.5.8 Connection to the VRM Portal
Connection of the product to VRM requires an internet connection. This can be made via wifi, or preferably a hardwired
ethernet cable to an internet connected router.
The VRM site id is located on a sticker inside the cable connections area of the device.
For more information to set up VRM, refer to the VRM Getting Started Manua
12


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Victron EasySolar-II 48 3000 35-32 MPPT 250 70 GX at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Victron EasySolar-II 48 3000 35-32 MPPT 250 70 GX in the language / languages: English, German, Dutch, French, Italian, Swedish, Spanish as an attachment in your email.

The manual is 2.84 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info