4.3.2 Li-ion batteries
Victron LiFePO4 Smart batteries
Use the VE.Bus BMS
4.3.3 Other Li-ion batteries
Please see https://www.victronenergy.com/live/battery_compatibility:start
4.3.4 More on batteries and battery charging
Our book 'Energy Unlimited' offers further information on batteries and battery charging, and is available free of charge
on our website: www.victronenergy.com/support-and-downloads/whitepapers
For more information on adaptive charging, please also refer to the General Technical Information on our website.
4.4 ESS Energy Storage Systems: feeding energy back into the grid
When the product is used in a configuration in which it will feed back energy into the grid it is required to enable grid code
compliance by selecting the appropriate grid code country setting with the VEConfigure tool.
Once set, a password will be required to disable grid code compliance or change grid code related parameters. Contact
your Victron Distributor if you require this password.
Depending on the grid code there are several reactive Power control modes:
Fixed cos φ
Cos φ as function of P
Fixed Q
Q as function of input voltage
Reactive Power capability
If the local grid code is not supported by the product an external certified interface device should be used to connect the
product to the grid.
The product can also be used as a bidirectional inverter operating parallel to the grid, integrated into a customer
designed system (PLC or other) that takes care of the control-loop and grid measurement,
Special note regarding NRS-097 (South Africa)
1. The maximum allowed impedance of the network is 0.28Ω + j0.18Ω
2. The inverter is fulfilling the unbalance requirement in case of multiple single phase units only when the Color
Control GX is part of the installation.
Special notes regarding AS 4777.2 (Australia/New Zealand)
1. Certification and CEC approval for off-grid use does NOT imply approval for grid-interactive installations.
Additional certification to IEC 62109.2 and AS 4777.2.2015 are required before grid-interactive systems can be
implemented. Please check the Clean Energy Council website for current approvals.
2. DRM Demand Response Mode When the AS4777.2 grid code has been selected in VEConfigure, DRM 0
functionality is available on port AUX1 (see appendix A. To enable grid connection, a resistance of between
5kOhm and 16kOhm must be present between the terminals of port AUX1 (marked + and - ). The product will
disconnect from the grid in case of an open circuit or a short circuit between the terminals of port AUX1. The
maximum voltage that may be present between the terminals of port AUX1 is 5V. Alternatively, if DRM 0 is not
required, this functionality can be disabled with VEConfigure.
7


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Victron EasySolar-II 48 3000 35-32 MPPT 250 70 GX at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Victron EasySolar-II 48 3000 35-32 MPPT 250 70 GX in the language / languages: English, German, Dutch, French, Italian, Swedish, Spanish as an attachment in your email.

The manual is 2.84 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info