6.4.1 Special display feature
When you have an extended VE.Bus system (or a Quattro system) and you use more than 1
AC input you might come across the following situation:
Assuming you use two AC inputs. You would like to give the generator priority over the shore
so you connect the generator to AC input 1. You do not want the user to adapt the current limit
set point of the generator so in VEConfigure2 you uncheck the ‘overruled by remote’ checkbox
for the current limit setting for AC input 1.
You connect the shore current to AC input 2. For AC Input 2 you leave the ‘overruled by
remote’ checkbox checked.
The DMC will then behave as follows:
If the generator is selected the DMC displays .
When the generator is switched off and shore current is applied, the DMC will display the set
point for AC input 2 alternating with the AC input identification .
This alternating might not be what you want or expect. There is only one current limit set point
that the user can change! When the other AC input is selected the display will always display
. It would be sufficient to display the current limit value when AC input 2 is selected
because that is enough indication for the operator that the system has switched to shore
current.
To achieve this, all but one of the “Upper Shore limits” must be programmed to zero.
So in this example the limits for AC1, AC3 and AC4 must be programmed to zero. The display
will then not alternate between and the set point for AC2.
Summary: Setting all but one of the “Upper Shore limits” to zero will stop the alternating of the
display.
6.5 Configuration examples
Two examples are given to help you understand the setting of the parameters.
Example 1: Two VE.Bus Multis 16A/230V + 4kVA gen. (3000 rpm) + external transfer switch.
Because this is a VE.Bus system the scaling factor does not need to be set.
A 4kVA generator can supply a maximum current of 17,4A. Using the 70% safety margin we will
set the generator current to 12A. To set the configuration, do the following:
1) Press and hold the configuration button until the bottom LED in the left column starts flashing.
This means you entered the configuration mode and you can change the scaling factor. As said
this parameter can be ignored in case of VE.Bus Multis.
2) Press the button to go to the next setting. The lower left LED will turn on indicating that the
generator current can be set.
3) Turn on the knob until the display indicates 12.
4) Press the button to advance to the “Upper Shore limit for AC input 1” setting.
5) If you want the maximum shore current the operator can set to be lower than 32 Amps you can
change this value.
6) Since the next 3 parameters (Upper Shore limit for AC input 2, 3 and 4) need not to be
configured you can press the button 4 times to step through the settings and finalize the
configuration.
14


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Victron Digital Multi Control 200A at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Victron Digital Multi Control 200A in the language / languages: English, German, Dutch, French, Spanish as an attachment in your email.

The manual is 0.41 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info