Example 2: Four non VE.Bus Multis 30A/120V + 13kVA gen. (1500 rpm) + external transfer
switch.
For this configuration the “scaling factor” must be calculated. The NrOfDevices is 4, the
DeviceType is 2 so the “scaling factor” is (4 x 2) 1 = 7
A 13kVA generator 120V can supply a maximum current of 108,3A. Using the 90% safety margin
we will set the generator current to 98A. To set the configuration, do the following:
1) Press and hold the configuration button until the bottom LED in the left column starts flashing.
This means you entered the configuration mode and you can change the scaling factor.
2) Turn on the knob until the display indicates 7.
3) Press the button to go to the next setting. The lower left LED will turn on indicating that the
generator current can be set.
4) Turn on the knob until the display indicates 98.
5) Press the button to advance to the “Upper Shore limit for AC input 1” setting
6) You probably want the maximum shore current the operator can set to be lower than 128 Amps
so turn the knob until the display indicates a proper maximum shore current.
7) Since the next 3 parameters (Upper Shore limit for AC input 2, 3 and 4) need not to be
configured you can press the button 4 times to step through the settings and finalize the
configuration.
15


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Victron Digital Multi Control 200 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Victron Digital Multi Control 200 in the language / languages: English, German, Dutch, French, Spanish as an attachment in your email.

The manual is 0.41 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info