6.2 Setting the scaling factor
Configuration of the scaling factor is only needed for non VE.Bus Multis. (All Multi firmware
versions 15xxyyy, 17xxyyy and 18xxyyy)
The scaling factor is used to match the currents displayed by the DMC to the currents in the
system.
The scaling factor is calculated using the formula:
Scaling factor = (NrOfDevices * DeviceType) - 1
The DeviceType is 1 for a 16A model Multi and 2 for a 30A model Multi.
NrOfDevices is all the Multis including the master Multi.
Example: You have four 30A Multis. The scaling factor is then: (4 * 2) 1 = 7
Important notes:
1) Do NOT specify the number of slaves (with VEConfigure2) in the Multis when you have
specified a Scaling factor other than zero!
In that case the number of slaves in the Multis must be set to zero!
The system will not work properly if you set the scaling factor in the DMC and the number of
slaves in the Multis!
2) When using a split-phase or 3-phase configuration, the NrOfDevices is determined by the
number of devices in 1 phase. So for a 3-phase system build with 6 Multis the NrOfDevices=2.
6.3 Setting the generator current limit
This parameter needs only to be configured when using an external transfer switch (PowerMan)
(see paragraph 3.1) and is of no influence otherwise.
The generator current limit can be set from 0 to 198 Amps in steps of 2 Amps.
Important note:
Small 3000 rpm generator sets of certain brands will overheat when operating for long periods at
full load. In some cases the maximum current will have to be set at no more than 70 % of the
rated maximum current. The current limit of 1500 rpm generator sets can in general be set at
around 90 % of the rated output current.
6.4 Setting the Upper Shore limits for AC input 1 to 4
To prevent that the operator of the DMC sets a too high current limit for the system an Upper
Shore limit can be set.
Example: You have a system with 5 Multis in parallel. The maximum feed through current would
be 80A. This might be a far too high setting for the circuit breakers used in your system. By
adjusting the “Upper Shore limit” you can prevent that the shore current limit is set higher than, for
instance, 30A.
Four different limits can be set because VE.Bus systems can have up to 4 AC inputs.
For simple VE.Bus systems with Multis or non VE.Bus systems it is sufficient to set only the
“Upper Shore limit for AC input 1”. The others will not be used then.
13


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Victron Digital Multi Control 200 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Victron Digital Multi Control 200 in the language / languages: English, German, Dutch, French, Spanish as an attachment in your email.

The manual is 0.41 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info