Battery charger / inverter COMBI-GAMMA
64 090138.02
E1-03: Udc Lower than ? Voltage
E1-04: Udc Lower for ? sec
Use these settings to switch the Aux-Relay 1 ON. When battery voltage becomes lower •
than a certain limit (E1-03) for a certain time (E1-04).
Note: If E1-04=0 sec (Initial setting), then E1-03 is ignored.*
E1-05: Udc Higher than ? Voltage
E1-06: Udc Higher for ? sec
Use these settings to switch the Aux-Relay 1 ON when battery voltage becomes higher •
than a certain limit (E1-05) for a certain time (E1-06).
Note: If E1-06=0 sec (Initial setting), then E1-05 is ignored.*
E1-07: Not Charge for ? sec
Use this setting to switch on the Aux-Relay 1 when the • AC CHARGER is not charging for
a certain time (E1-07).
Normally used for generating an alarm situation.•
E1-08: Fan ON for ? sec
This will switch the Aux-Relay 1 ON when the internal fan switches on. This can be used •
together with the E2-08: Fan OFF for ? sec setting to drive an external fan.
E1-09: When bulk protection is activated.
This will set the Aux-Relay1 ON when the “bulk protection” (D1-09=1) is activated. This •
condition will remain valid as long as the AC CHARGER is disabled due to that safety
mechanism. One can use this setting to generate an alarm.
E1-10: System Fault Occurs
This will switch on the Aux-Relay 1 when the Combi-Gamma switches off due to an in-•
ternal alarm situation.
E1-11: Temp. Alarm Select (When E1-12=0, ignore this setting)
E1-12: Temp. Alarm for ? sec
If you want to switch on the Aux-Relay 1 when there is a over temperature alarm, this •
setting (E1-11) can be used to choose between pre-alarm or normal alarm.
As with other Aux-Relay 1 settings, a delay value (E1-12) must be specified also. This •
can be done with Delay value for set Aux-Relay 1 ON when over temperature alarm (E1-
12) setting.
E1-13: Low Batt. Alarm Select (When E1-14=0, ignore this setting)
E1-14: Low Batt. Alarm for ? sec
If you want to switch on the Aux-Relay 1 when there is a low battery alarm, this setting •
64


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Vetus COMBI3012 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Vetus COMBI3012 in the language / languages: English as an attachment in your email.

The manual is 4,72 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Vetus COMBI3012

Vetus COMBI3012 Usermanual and installation guide - Dutch - 80 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info