090138.02 63
D1-09: Stop After 10Hr Bulk
This is a safety setting. When the bulk phase lasts more than 10 hours, this can be indi-•
cation that a battery cell is damaged.
The absorption voltage (or the 14.4V for battery when • Battery Safe (D1-02=3) mode is
used) will never be reached in that case and the other cells will be over-charged result-
ing in the production of an explosive gas.
Therefore, the charger is disabled if the bulk phase lasts more than 10 hours.•
This setting can be disabled because it does not always indicate a problem when the bulk •
phase lasts very long. The charge current can be very low due to limited AC input current
and/or AC loads. Also, DC loads can “steal away” part of the charge current. In that case,
the bulk phase will need more time to complete and this setting must be disabled.
Note: When this setting is disabled, there is no safety check to protect against *
over-charging.
Setting Function
D1-09=0 Stop After 10Hr Bulk setting is disabled
D1-09=1
(Initial setting)
Stop After 10Hr Bulk setting is enabled
D1-10: Equalize Mode Select (Storage Mode Select)
This setting is used for enabling/disabling the Equalize Mode.•
In this mode, the voltage setpoint is 13.2V (for 12V battery). If Equalize mode is disabled, •
then the normal float voltage will be used.
Setting Function
D1-10=0 Equalize mode is disabled
D1-10=1
(Initial setting)
Equalize mode is enabled
E Group (Auxiliary Relay):
E1 Group (Setting Aux-Relay 1 ON Condition)
E1-01: LOAD Higher than ? Amps
E1-02: LOAD Higher for ? sec
Use these settings to switch the Aux-Relay 1 ON. When the actual AC OUT load is above •
a certain value (E1-01) for a certain time (E1-02).
The corresponding Aux-Relay 1 OFF condition is•
E2-01: Load Lower than ? Amps and
E2-02: Load Lower for ? sec.
Note: If setting E1-02=0 sec (Initial setting). Then the E1-01 is ignored.*
Note: If setting E2-02=0 sec (Initial setting). Then the E2-01 is ignored.*
63


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Vetus COMBI3012 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Vetus COMBI3012 in the language / languages: English as an attachment in your email.

The manual is 4,72 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Vetus COMBI3012

Vetus COMBI3012 Usermanual and installation guide - Dutch - 80 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info