Pellet storage
The storage should be designed so that there are no unnecessary dust and chips at filling to avoid problems
like vaulting of the pellets. Therefore we recommend completed storages from MAFA i Ängelholm.
In cooperation with MAFA we can offer
two models of week storages that we
recommend MAFA MINI that holds 300
liters and MAFA MIDI that holds 730
liters. These storages are most suitable
when using pellets in small bags. For
houses and smaller real estates bulk
deliveries is the most comfortable,
effective and cheapest way to handle
fuel pellets.
MAFA MINI week storage ( 300liter)
The suitability of the boiler
The Ulma Eco can be installed in almost all existing boiler on the market. It is important that he hearth is so
big that he flame does not touch water cooled walls. There should also be room the ash. The smoke flues of
the boiler may not be so narrow that they clog of the ash. Wood boilers have the advantage that they often
have larger room for the ash and are easier to sweep, but even most oil fired boilers are suitable for Ulma
Basic. When choosing where to place it a double boiler, make sure if there is a big difference between given
effect between oil and wood. If the difference does not go over 10kw, the pellet burner should be placed in
the wood door if it is possible to open the door with the burner mounted. A boiler meant for high efficiency
more than 100kw can give too low flue gas temperatures
(see the chapter chimney).
The chimney
The chimney should be inspected and possibly test pressured before installation if it has not been operating
before and had continuous maintenance from the local chimney sweeper. At smallest doubt contact your
certified chimney sweeper for inspection. Please note that at too low flue gas temperature the flue gases may
condense with risk of frost damages on the chimney as result. As a rule of thumb you should aim at a flue
gas temperature of at least 70-80°C 1m down in the chimney when the burner is burning, this goes first of all
for brick chimneys or similar material. The choice of flue gas temperature depends on the design and
isolation, a steel chimney or walled chimney with flue lining tube are not as easily damaged of low flue gas
temperatures, provided that possible condensate is drained continuously from the lowest point of the
chimney. This is the task of the installer to control at the installation.
If the chimney is already equipped with a chimney damper this should be completely open at pellet firing. If
possible lock this in some way in open position.
We recommend installation of draft limiter (Back draft door)
The draft limiter shall at installation be adjusted by the installer of approx. -0,10/- 0.15 hPa under pressure.
The draft limiter also helps ventilate the chimney and minimize the risk of condensate problems. We
recommend that it is mounted on the flue pipe out from the boiler. It should be placed so that flue gas
measurements could be made before the draft limiter.
Flue gas thermometer
Provide your installation with a flue gas thermometer. Here you can easily see when the temperature rises
and it is time to clean the installation. Suitable temperature rising is approx. 40-50 degrees. But you should
also overlook the capacity of the boiler on hearth and convection part to take care of the ash amount in good
time. The tighter intervals give better fuel economy and efficiency.
Flue gas analysis
At installation the unit should always be adjusted with a flue gas instrument and not only with help from the
human eye. When the burner is in place and has been trimmed in with a flue gas instrument a print of the
control measurements of the installer should be made. You should be able to read values like CO, O2, CO2,
8


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Ulma 40 Kw at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Ulma 40 Kw in the language / languages: English as an attachment in your email.

The manual is 1,46 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Ulma 40 Kw

Ulma 40 Kw User Manual - Dutch - 10 pages

Ulma 40 Kw User Manual - French - 10 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info