local air conditioner PAC 2100 X / PAC 2600 X
The device works with reduced or no cooling capacity:
Check whether cooling mode is selected.
Check the proper fit of the exhaust air hose. In case of
kinks, bends or blockage in the hose, exhaust air cannot
be discharged. Clear the way for the exhaust air.
Check the position of the ventilation flaps. They should be
opened to the maximum.
Check the air filter(s) for dirt. If necessary, clean or replace
the air filter(s).
Check the minimum distance to walls or other objects.
Position the device a little more in the room's centre
if required.
Check whether any windows and/or doors of the room are
open. If so, close them. One window has to remain open
for the exhaust air hose nonetheless.
Check the temperature setting at the device. Reduce the
set temperature if it is higher than the room temperature.
The device is loud or vibrates:
Check whether the device is set up in a stable and upright
position.
Condensate is leaking:
Check the device for leaks.
The compressor does not start:
Check whether the overheating protection of the
compressor has tripped. Disconnect the device from the
mains and let it cool down for approx. 10minutes before
reconnecting it.
Check whether the ambient temperature equals the target
temperature (in cooling mode). The compressor will not
switch on unless the respective temperature is reached.
The compressor may start up with a delay of 3minutes, as
it is provided with an internal protection against direct
restart.
The device gets very warm, is loud or loses power:
Check the air inlets and air filters for dirt. Remove external
dirt.
From the outside, check the device for dirt (see chapter
Maintenance). If the inside of the device is dirty, have it
cleaned by a specialist company for cooling and
air-conditioning or by Trotec.
The device does not respond to the infrared remote control:
Check whether the distance between remote control and
device is too large and reduce it if necessary.
Make sure there are no obstacles, such as furniture or
walls, between the device and the remote control. Ensure
visual contact between device and remote control.
Check the charging status of the batteries and change
them if required.
If the batteries have only just been changed, check them
for correct polarity and change them if required.
Check whether the remote control is still in standby mode.
Standby mode can be terminated by pressing the
ON/OFF button(28) on the remote control.
Note
Wait for at least 3 minutes after maintenance and
repair work. Only then switch the device back on.
Your device still does not operate correctly after these
checks?
Please contact the customer service. If necessary, bring the
device to a specialist company for cooling and air-conditioning
or to Trotec for repair.
Error codes
The following error messages can be displayed in the segment
display(15):
Error code Cause Remedy
E1 Fault at
temperature
sensor
Disconnect the device briefly
from the mains.
Should the error still be
displayed after the restart,
please contact the customer
service.
E2 Fault at humidity
sensor
E4 Fault at control
panel
P1 Condensation
tank full
Empty the condensation tank.
Should the error still be
displayed, please contact the
customer service.
15


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Trotec PAC2100X at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Trotec PAC2100X in the language / languages: English as an attachment in your email.

The manual is 0,71 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Trotec PAC2100X

Trotec PAC2100X User Manual - German - 22 pages

Trotec PAC2100X User Manual - Dutch - 22 pages

Trotec PAC2100X User Manual - French - 23 pages

Trotec PAC2100X User Manual - Spanish - 23 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info