8.3 Installation instructions regarding existing flues. (see APPENDIX 3)
Instructions
The flue gas exhaust system falls within category C91 and must be built in accordance with national
rules and regulations and the instructions of the manufacturer, as specified in the documentation and
installation instructions.
This means, among other things, that the existing chimney must not be smaller than 150 mm
round / square, but no larger than 200 mm, and not ventilated by grilles etc. In the case of larger chimney
size, a flexible hose of around 150 mm may possibly be used in combination with a flexible hose of around
100 mm, as described below. For other situations, you should consult your supplier / manufacturer.
8.4 Components
Check all parts for damage before commencing the installation. You will require the following parts for
converting a brickwork duct to a balanced flue concentric duct :
Note: The renovation kit consists of parts 4, 5 and 7.
8.5 Installation
* Guide the flexible hose (6) through the existing duct.
* Attach the adjustable pipe (5) to the bottom of the flexible hose and secure this in place using 2 parkers.
* Level the bottom side of the adjustable pipe (5) with the ceiling of existing chimney.
* Shorten the flexible hose to approximately 100 mm above the existing chimney top.
* Attach the mounting plate / connecting piece (7) to the flexible hose on the roof. Clamp it with a hose
band and secure it in place using a parker.
* Attach the mounting plate / connecting piece (7) to the chimney top, using silicone sealant to make it
watertight secure with stainless steel screws.
* Install the roof terminal (9) and secure it in place using the supplied locking band (8).
* The adjustable pipe (5) will stick about 100mm below ceiling/existing chimney. Mount the inner ceiling
plate (4) gastight to the ceiling/existing chimney with silicone kit and fixing screws.
* Position the unit in accordance with the instructions of the unit manufacturer.
* Always install a minimum of 1 metre of concentric duct type THC CC100-150 (2), or 130-200 mm with
reduction to 100-150 mm.
8.6. Cleaning and maintenance.
This appliance should be inspected and serviced once a year by a qualified, competent and registered person.
The inspection and maintenance must at least ensure that the appliance is working correctly and safely.
It is advisable to clean the appliance of any dust and debris before regularly during the heating season and
especially if the appliance has not been used for some time. This can be done with a soft brush and a vacuum
cleaner or a damp cloth and if required a non-abrasive cleaning agent. Do not use corrosive or abrasive
substances to clean the appliance.
The Concentric flue system must be inspected and cleaned every 2 years.
Also control of:
1 Gas tightness of gas fire and concentric flue system.
2 The correct operation of the gas control and the ignition of the burner.
12


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Thermocet Trimline Quadro 46 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Thermocet Trimline Quadro 46 in the language / languages: English, German, Dutch, Danish, French, Spanish as an attachment in your email.

The manual is 7,56 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Thermocet Trimline Quadro 46

Thermocet Trimline Quadro 46 User Manual - English - 85 pages

Thermocet Trimline Quadro 46 Usermanual and installation guide - English - 34 pages

Thermocet Trimline Quadro 46 User Manual - German, Dutch - 85 pages

Thermocet Trimline Quadro 46 Usermanual and installation guide - Dutch - 34 pages

Thermocet Trimline Quadro 46 User Manual - Danish, French, Spanish - 85 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info