532670
11
Zoom out
Zoom in
Previous page
1/85
Next page
Page.10
The concentric flue system is composed of an inner- and an outer tube.
These tubes are concentrically arranged; through the inner tube, the combustion gases are evacuated and the fresh
combustion air is supplied between the inner and outer tube.
8.1 Components of the concentric flue system.
Different connections are possible using the concentric flue system. These are:
Through the roof face and through the exterior wall.
There are various options for mounting the lay outs for this system,
however, there are a few important requirements/conditions:
* The maximum recommended vertical flue length is 12 metres (the sum of the flue length and the
calculation lengths for the bends).
* 90° bends have a 2-metre horizontal calculation length.
* 45° bends have a 1-metre horizontal calculation length.
* The outlet can be installed at any point on the roof face or exterior wall (supply and discharge in
an identical pressure area), but must meet applicable regulations.
* Ducts may not be insulated.
8.2 Construction of concentric flue system
Indirect wall connection.
* The outlet may be installed in the wall, taking any hindrance to the surrounding area into consideration,
according to national, regional, local standards and regulations.
Ensure wind pressure on the flue terminal is not too extreme, such as a balcony, flat roof,
corners and in small alleys etc., as this may negatively influence the unit efficiency.
* Provide a recess in the exterior wall of around 155 mm for concentric 100-150, and 205 mm for
concentric 130-200. (in a flammable wall ensure there is 50 mm of extra space around the outer
pipe and use fireproof casing) and fix the exterior wall duct with the wall plate to the outer side of
the wall. The wall plate of the exterior wall duct must be sealed sufficiently against the wall on
the outside, to avoid moisture and/or flue gas leaks into the living space.
* The flue should be cased if necessary. Sufficient fireproof measures must also be taken when
the flue is being mounted along flammable materials.
* Determine the position of the unit and outlet and begin construction of the flue with the connection
on the unit, paying attention to the direction of installation and connecting the elements by means
of locking bands.
* An adjustable length can be used between the bends or when connecting to the unit.
If necessary, use wall brackets to support the flue.
Rooftermination.
* The flue terminal can be located at any random place on the roof face (supply and exhaust in
identical pressure areas) and must meet the applicable rules and regulations.
* A roof flashing for a flat roof or a lead flashing for sloping tiled roofs can be used for a
watertight connection. Use various elbows for making the proper connection, if required.
The recess in the roof decking should be 5 cm larger all around, to ensure sufficient fire resistance.
* One needs to take into account the regulation regarding fire resistance between rooms
(See national, regional, local standards and regulations). A casing made of fireproof material
(e.g. 12 mm Promatect fire resistant plate) must be used at 25mm from the outside duct.
* Determine the position of the unit and outlet and begin construction of the flue with the connection
on the unit (always 1 metre vertical first), paying attention to the direction of installation!
The flue must be installed dripless. Connect the elements by using locking bands.
Ensure the gas tightness of all connections is correct.
* An adjustable length can be used between the elbows or when making the connection to the unit
and/or the roof terminal. Use 2 wall brackets to support the flue on each floor.
8. CONCENTRIC CHIMNEY LAY OUT
NOTICE
Ensure the restriction plate in the fire is mounted in the correct manner, as indicated in these instructions.
The correct restriction plate will provide the unit with the most optimal efficiency, flame image and combustion.
Mounting an incorrectly placed restriction plate may cause malfunction of the unit.
11


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Thermocet Trimline Quadro 46 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Thermocet Trimline Quadro 46 in the language / languages: English, German, Dutch, Danish, French, Spanish as an attachment in your email.

The manual is 7,56 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Thermocet Trimline Quadro 46

Thermocet Trimline Quadro 46 User Manual - English - 85 pages

Thermocet Trimline Quadro 46 Usermanual and installation guide - English - 34 pages

Thermocet Trimline Quadro 46 User Manual - German, Dutch - 85 pages

Thermocet Trimline Quadro 46 Usermanual and installation guide - Dutch - 34 pages

Thermocet Trimline Quadro 46 User Manual - Danish, French, Spanish - 85 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info