593166
14
Zoom out
Zoom in
Previous page
1/75
Next page
- 26 - - 27 -
The master/slave configuration
permits detection of movement in
large-type rooms or spaces (load
connected = master, no load =
slave). The level of brightness pre-
vailing in the room is only evaluat-
ed at the master. The slaves report
movements detected to the mas-
ter. Lighting or HVAC is switched
'ON' and 'OFF' by the master only.
Master/slave
A parallel-connected configuration
also permits the use of several
masters. In this case, each master
operates the lighting group in
accordance with the level of
brightness it measures. Delay
times and brightness thresholds
are selected at each master as re-
quired. The switched load is spread
among the individual masters.
Presence is still detected collec-
tively by all detectors. The pres-
ence output can be picked off
from any master.
Master/master
Remote control
Using the remote control (option-
al), functions can be conveniently
activated from the floor.
Note: The pulse mode cannot be
overridden by the remote control.
Switch pulse mode 'OFF' manually.
Presence Control remote control
unit: EAN no.: 4007841 000387
Parallel-connected configurations
Two detectors linked with an
external stairwell lighting
timer
Old building / building moderni-
sation
External light source activated by
button. No twilight mode, day
mode only.
Detector as stairwell lighting
timer
14.1
14.2
14.3
14.4
When using several detectors, they must be connected to the same phase!
DIM detector
14.5
Setting 1 sec. – 2 hr.
Turned fully clockwise: max
Turned fully anti-clockwise: min
Setting 0 sec. – 10 min.
Turned fully clockwise:
Room surveillance
Turned fully anti-clockwise:
0 sec. ('OFF')
Turning the potentiometer to the
"Surveillance" setting reduces the
sensitivity of the "Presence"
switching output. The contact only
closes on detecting a pronounced
movement, signalising with a high
degree of certainty that persons
are present.
The stay-'ON- time remains
active. The switch-'ON' delay
is inactivated.
Switch-'ON' delay for switching output 2 HVAC
Reach adjustment
COM 2
Potentiometer
Potentiometer
Provides basic illumination for the
selected stay-'ON' time when ambi-
ent light falls below the selected
brightness threshold that is set. This
can be dimmed to 10% of maxi-
mum light intensity. As soon as a
person enters the scene, the detec-
tor switches either to 100% light
intensity (constant-lighting control-
ler 'OFF') or adjusts to the preselect-
ed brightness level (constant-light-
ing controller 'ON'). When no move-
ment is being detected, the detec-
tor dims back to basic brightness
after the stay-'ON' time expires. This
is switched 'OFF' when stay-'ON'
time (1 min. – 30 min.) has expired
or the daylight component is suffi-
cient to exceed the selected level of
brightness. In the 'ON' setting, the
detector switches basic brightness
'ON' and 'OFF' as soon as the level
of light falls below the brightness
threshold.
Basic brightness (DIM option)
Potentiometer
Stay-'ON' time for switching output 2 HVAC
The reach required (response
threshold) is infinitely variable.
HF 360
1 m min. – 8 m max.
DUAL HF
min. 3 x 3 m – 10 x 3 m in
each direction
Turned fully anticlockwise
(factory setting) = minimum reach
Turned fully clockwise
(factory setting) = maximum reach
Potentiometer
GB
PC PRO HF360_DualHF_Zentraleuropa.indd 26-27PC PRO HF360_DualHF_Zentraleuropa.indd 26-27 11.09.13 10:3811.09.13 10:38
14


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Steinel DUAL HF COM at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Steinel DUAL HF COM in the language / languages: All languages as an attachment in your email.

The manual is 2 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info