Purging time
If the temperature on the collector sensor increases within a minute by the value defined under “increase”, the solar circulation
pump will be turned on for the set “purging time so that the medium to be measured is transported to the collector sensor. If when
the set ΔT is reached this does not switch on, a 5-minute circulation pause time for the starting aid function will apply.
Increase
If the temperature at the collector reaches within a minute the value defined, the solar pump is turned on for the duration of the
purging time.
Protective functions for Solar
The protection functions for Solar are not displayed in the “Protective functions” menu, but rather as a sub-menu in the
settings from the solar function, see " Solar " on page 35.
System protection
Priority protection function
The system protection should prevent an overheating of the components installed in the system through the forced shut down of
the solar circulation pump. If the value “AS Ton” on the collector has been exceeded for 1 Min. the pump will be turned off and not
turn on again in order to protect the collector, for example, from steam. The pump is turned on again when the value “AS Toff” on
the collector has not been met.
With the system protection (on), there are increased standstill temperatures in the solar collector and therefore an
increased pressure in the system. The operating manuals from the system components must be observed.
Collector protection
Priority protection function
The collector protection prevents the collector from overheating. A forced switching of the pump makes sure that the collector is
cooled through the storage. If the value “KS Ton” is exceeded on the collector, the pump will be turned on in order to cool the col-
lector. The pump is shut down if the value “KS Toff” on the collector is not met or the value “KS Tmax Sp.” on the storage or KS SB
Max on the pool is exceeded.
System protection has priority over collector protection! Even if the switch requirements for the collector protection are
present, the solar circulation pump is turned off once “AS T on is reached. Normally the values from the system pro-
tection (depending on the maximum temperature of the storage or other components) are higher than the collector pro-
tection.
Recooling
In the system hydraulics with solar, excess energy is guided from the storage back to the collector with an activated return cooling
function. This only occurs if the temperature in the storage is greater than the value “Return cooling Tref” and the collector is at
least 20 °C colder than the storage and until the storage temperature has fallen below the value “Return cooling Tref”. For muti-
storage systems, the return cooling applies to all storage.
Energy is lost through the collector through this function! The recooling should only be activated in cases of exception,
with low heat acceptance, for example, during vacation.
Frost Protection
A 2-level frost protection function can be activated. In level 1, the controller turns on the pump every hour for 1 minute if the col-
lector temperature is below the set value “Frost Level 1”. If the collector temperature continues to decrease to the set value “Frost
Level 2”, the controller will turn on the pump without disruption. If the collector temperature exceeds the value “Frost level 2 by 2
°C, the pump will turn off again.
Energy is lost through the collector through this function! It is normally not activated for solar systems with antifreeze.
The operating manuals from the other system components must be observed.
Collector alarm
If this temperature at the collector sensor is exceeded when the solar pump is turned on, a warning or error notification is
triggered. There is a corresponding warning in the display.
Collector
Collector sensor
The collector sensor can be determined or changed here. The collector sensor set here is used for solar function ( Tmin collector,
∆T Solar,....) as well as all protection functions Solar (collector protection, system protection, ...).
Solar storage
The solar storage sensor can be determined or changed here. The solar storage sensor determined here is used for the solar
function ( Tmax storage, ∆T Solar,....).
36
36


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Sorel XHCC S62 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Sorel XHCC S62 in the language / languages: English as an attachment in your email.

The manual is 3 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Sorel XHCC S62

Sorel XHCC S62 User Manual - German - 62 pages

Sorel XHCC S62 User Manual - French - 44 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info