Gylcol pump lag
After shutting down the compressor, the pump remains on for the time set here.
Cooling
In this menu, the cooling function is activated, and the mode of cooling function is set.
Heating Circuit: In the Heating Circuit modus, the heating circuit is used for room cooling. This may be a surface heating circuit or
a radiator heating circuit. For this operating mode, a room thermostat with humidity sensor is required (e.g. RC22, ° CALEON
Clima).
Air conditioning:Through the air conditioning modus, fan coils connected through the heating circuit may be activated for room
cooling.
Single: In this modus, the switch contact is switched in regards to the assigned sensor for the cooling of the measured
Temperature in order to control external air conditioning for room cooling.
Off: Cooling function is disabled.
Sensor cooling
Here the affiliated sensor is set for the cooling function in the Simple modus. If theset temperature on this sensor is exceeded, the
relay will turn on for the cooling function. If the set temperature on this sensor is exceeded bz the hysteresis, the relay will turn on
for the cooling function.
Max. flow cooling
This value is the upper limit of the reference flow temperature of the cooling.
Min. flow cooling
This value is the lower limit of the reference flow temperature of the cooling.
Cool storage
The storage can be cooled through this function.
Yes: The flow and buffer storage are cooled down to the reference flow temperature + hysteresis.
No: It is cooled down to the reference flow temperature + hysteresis, the temperature in the buffer storage is ignored.
By default, sensor S2 is set as the buffer sensor. Theassigned sensor for this function can be changed in the settings for the heat-
ing circuit 1 see " Buffer sensor " on page 28.
Dew point correction
The internal dew point curve is moved parallel with this value. The dew point calculation is used to calculate at which room tem-
perature there is an undesired condensation (precipitation) at the currently measured humidity. This calculated room temperature
will not be undershot with the cooling system and therefore represents a temperature lower limit for the cooling system.
The calculated room temperature can be moved by up to 10 °C with the dew point correction.
Example 1: You determine that there is precipitation with the default value,
so you increase this correction value.
Example 2: Condensation/precipitation can be ignored, instead a
stronger cooling system is required. You therefore decrease this correction value.
In case of reduction of the calculated temperature with the help of dew point correction condensation / perspiration / pre-
cipitation can occur, which, among other things, may cause the formation of mold.
Room reference cooling
Reference value for the temperature in the room.
The controller adjusts the flow so that this temperature is reached in the room.
If the value set here is exceeded, the relay will turn on the cooling function if this is approved for the time.
The relay of the cooling function is turned off if the reference value hysteresis is not met.
Delay
Switch delay of the heat and cooling request. In order to prevent the heat or cooling request to be activated if there are heat devi-
ations, the corresponding relay is switched up ot 5 minutes before the switch conditions occur.
Periods
Cooling activity times
Here the desired periods are set in which the cooling function is approved. For each weekday, three times can be specified, fur-
thermore, you can copy individual day to other days. The cooling function is shut down outside of the set times.
34
34


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Sorel XHCC S61 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Sorel XHCC S61 in the language / languages: English as an attachment in your email.

The manual is 3 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Sorel XHCC S61

Sorel XHCC S61 User Manual - German - 44 pages

Sorel XHCC S61 User Manual - French - 44 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info