12.7 Heat pump system Menus 7.7 / 7.7.1 - 7.7.6
12.7.1 Heat pump runtime Menu 7.7.1
After a heat demand, the compressor remains switched on for at least the
time set here, even if the reference value has been reached.
Setting range: from 0 to 30 minutes / default setting: 10 minutes
If a switch-off condition from one of the protective functions set under
11. is present, the compressor switches off, even if the minimum
runtime has still not been reached.
Caution
12.7.3 Heat pump delay Menu 7.7.3
When there is a heat demand, rst the glycol pump, and if applicable, the
storage tank charging pump and domestic hot water pump/valve is switched
on for the time set here. Only after that is the compressor switched on.
Setting range: from 0 to 300 seconds / default setting: 20 seconds
12.7.4 Glycol overrun Menu 7.7.4
When the compressor is switched off, the glycol pump continues to run for
the time set here, and then switches off.
Setting range: from 0 to 300 seconds / default setting: 20 seconds
12.7.2 Heat pump idle time Menu 7.7.2
After previous operation, the compressor remains switched off for at least
the time set here, even if there is a demand.
Setting range: from 0 to 30 minutes / default setting: 10 minutes
The settings under this menu item and its four submenus should only be
made by a specialist, since they have fundamental effects on the function
of the heat pump and the connected system!
Special functions Menu 7
12 12
12.7.5 Storage tank charging pump (SCP) overrun Menu 7.7.5
When the compressor is switched off, the storage tank charging pump
continues to run for the set time in order to remove the residual heat from
the heat pump.
Setting range: from 0 to 300 seconds / default setting: 20 seconds
12.7.6 Heating circuit pump Menu 7.7.6
This setting is used to de ne whether the heating circuit pump is only
dependent on the outdoor temperature (summer/winter changeover=SW),
or should also be switched off if the reference value is exceeded
(Flow=VL).
If ow is selected, the times set under 12.7.3-12.7.5 are valid; they apply
to both the storage tank charging pump and the heating circuit pump.
Setting range: SW or VL ( ow) / default setting: SW
Caution
If VL is set, the heating circuit pump is switched on in winter mode
every 15 minutes in order to update the temperature value at the
heating circuit sensor. If the heating circuit sensor is installed in the
buffer storage tank, only the setting SW should be selected!
32


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Sorel WPC5 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Sorel WPC5 in the language / languages: English as an attachment in your email.

The manual is 2.42 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Sorel WPC5

Sorel WPC5 User Manual - German - 40 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info