Primary Mixer
When this function is activated, water is mixed in the primary circuit by a mixer via the primary return. As a result, less energy is drawn
from the storage tank at high storage tank temperatures, depending on the flow rate, since energy is mixed from the return flow.
Primary flow temp.
The primary mixer controls the primary temperature at S5 to the set value. In order to reach the set loading temperature on the sec-
ondary side, this value should be at least 2K higher than the set storage target temperature + switch-off hysteresis.
Example: Storage target temperature: 60 °C; switch-off hysteresis: 5 °C
In this case, the primary target value should be at least 67 °C (60 °C + 5 °C + 2 °C).
Direction open=left
Direction of the mixing valve can be set here.
Turn Time
Length of turn time.
Pause Factor
Adjustment of mixer pause time.
Burner
This function requests a burner when a request of a heating circuit or the DHW function is present. Depending on the request, the burner
will turn on in a more economic manner in the Eco-Mode if the solar circulation pump is running.
Burner sensor
Reference sensor for burner function. If this temperature at the set sensor is exceeded, the burner is shut down.
Delay
Switch delay, valid for cooling and heat request. The burner first turns on after this time span if the switch conditions were reached and
are still present. This feature prevents unnecessary switching by temperature fluctuations or gives time for a renewable energy source to
generate energy.
Tmax
Maximum temperature at the burner sensor. If this temperature at the set sensor is exceeded, the burner is shut down.
Parallel operation V1/V2
Switches the selected relay in parallel with the 0-10 V / PMW output V1/V2.
Switch parallel operation on, off or inverted.
Delay
The assigned relay switches on the delay set here later than V1/V2.
Follow-up time
The assigned relay switched on for the time set here longer than V1/V2.
Always on
The selected relay is always switched on.
Activate or deactivate "Always on"
For high-efficiency pumps with 0-10 V / PWM signal input, the power supply can be made via the additional functions "always
on" or "parallel operation V1/V2" on relays 1-3.
Signal V2
With this function, the PMW / 0-10 V output 2 can also be used to control an additional high-efficiency pump. If a pump function is activ-
ated (e. g. circulation, solar, additional pump,...), additional settings for pump settings V2 and speed control V2 can be set or adjusted.
17
17


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Sorel SLC at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Sorel SLC in the language / languages: English as an attachment in your email.

The manual is 3.76 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Sorel SLC

Sorel SLC User Manual - German - 21 pages

Sorel SLC User Manual - Dutch - 36 pages

Sorel SLC User Manual - French - 22 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info