Day Correction
Parallel characteristic translation
The day correction causes a parallel shift of the heating curve during daytime operating hours, because with certain outdoor tem-
peratures the building might not be optimally heated with the set heating curve. With a non-optimised heating curve, the following
situations frequently occur: hot weather = room too cold/cold weather = room too hot. In this case, the slope of the curve should
be reduced stepwise by 0.2 points and increases the day correction
by 2 ... 4 °C each.
Night Correction
Parallel characteristic translation
The night correction produces a parallel translation of the heating characteristic during the nighttime operating hours. If a neg-
ative value is set for the night correction, the reference flow temperature is lowered accordingly during the nighttime operating
hours. In this manner, primarily at night, but also during the day when no-one is at home, the room temperature is lowered, thus
saving energy. Example: A day correction of +5 °C and a night correction of -2 °C produces a reference flow temperature in night-
time operation that is 7 °C lower.
Comfort Temperature Boost
Parallel characteristic translation
The comfort temperature boost is added to the set day correction. In this manner it is possible to carry out quick heating and/or
raise the temperature of living spaces at a certain time each day.
Min. Flow
The minimum flow temperature is the lower limit of the heating curve, and by this, the reference flow temperature of the heating cir-
cuit. In addition to that, the minimal flow temperature is the reference flow temperature for the frost protection function.
Max. Flow
This value is the upper limit of the reference flow temperature of the heating circuit If however, the temperature of the heating cir-
cuit exceeds the set value, the heat circuit shuts down until the temperature falls below this value. The system purged for 30
seconds every 5 minutes.
The customer must provide an additional limiting thermostat which is connected to the pumps in series (eg underfloor
heating) for safety.
Energy Saving Mode
The Energy saving mode switches the heating on when T eco is undershot and heats up to T eco + hysteresis when solar charge
or solid fuel boiler is active.
Reference/Actual -
Switch on hysteresis for additional heating
This setting determines the allowed undershoot of the heating circuit temperature below the calculated reference fl ow tem-
perature. If the heating circuit flow temperature and the storage temperature drop below the reference flow temperature by this
value, the additional heating will start the additional heat source after a 1 minute delay.
Heat request is started when the flow temperature is continuously below reference temperature for 1 minute.
Threshold
For Energy saving mode
When Energy saving mode is active: During solar loading Threshold is used instead of TH set. When the temperature drops
below T eco at thermostat sensor 1, the relay is switched on and heats up to Threshold + hysteresis.
Mod. Offset
At modulated heat request the requested temperature can be increased by the value adjusted here.
14-day Reference
If operating mode‚ 14-day reference value is selected see " Heating Circuit " on page 15, the reference flow temperature for each
of the 14 days can be set here. In Menu 4.4.1, the starting time of the program is shown. To restart the reference program, press
restart‘.
Pressing restart again will reset the 14-day reference program and restart it at Day 1.
17
17


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Sorel MHCC at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Sorel MHCC in the language / languages: English as an attachment in your email.

The manual is 3.18 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Sorel MHCC

Sorel MHCC User Manual - German - 24 pages

Sorel MHCC User Manual - French - 36 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info