Event number Message, cause and corrective measures
6002 to 6412
Self diagnosis > Interference device
The cause must be determined by the Service.
Corrective measures:
Contact the Service (see Section15 "Contact", page96).
6502
Self-diagnosis > Overtemperature
The inverter has switched off due to excessive temperature.
Corrective measures:
Clean the cooling fins on the rear of the enclosure and the air ducts on
the top using a soft brush.
Ensure that the inverter has sufficient ventilation.
Ensure that the ambient temperature +40°C has not been exceeded.
Ensure that the inverter is not exposed to direct solar irradiation.
6512
Minimum operating temperature not reached
The inverter will only recommence grid feed-in once the temperature has
reached at least −25°C.
6603 to 6604
Self-diagnosis > Overload
The cause must be determined by the Service.
Corrective measures:
Contact the Service (see Section15 "Contact", page96).
6701 to 6702
Communication disturbed
Error in the communication processor, the inverter continues feeding in, how-
ever. The cause must be determined by the Service.
Corrective measures:
If this message is displayed frequently, contact the Service (see
Section15 "Contact", page96).
12Troubleshooting
SMA Solar Technology AG
Operating ManualSB30-50-1AV-40-BE-en-1068
68


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for SMA Sunny Boy 5.0 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of SMA Sunny Boy 5.0 in the language / languages: English as an attachment in your email.

The manual is 2,56 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of SMA Sunny Boy 5.0

SMA Sunny Boy 5.0 User Manual - German - 104 pages

SMA Sunny Boy 5.0 User Manual - Dutch - 102 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info