Event number Message, cause and corrective measures
3401 to 3407
DC overvoltage > Disconnect generator
Overvoltage at the DC input. This can destroy the inverter.
This message is signalized additionally by rapid flashing of the LEDs.
Corrective measures:
Immediately disconnect the inverter from all voltage sources (see
Section10, page60).
Check whether the DC voltage is below the maximum input voltage of
the inverter. If the DC voltage is below the maximum input voltage of the
inverter, reconnect the DC connectors to the inverter.
If the DC voltage exceeds the maximum input voltage of the inverter,
ensure that the PV array has been correctly rated or contact the installer
of the PV array.
If this message is repeated frequently, contact the Service (see
Section15 "Contact", page96).
3501
Insulation failure > Check generator
The inverter has detected a ground fault in the PV array.
Corrective measures:
Check the PV system for ground faults (see Section12.3, page80).
3701
Resid.curr.too.high > Check generator
The inverter has detected a residual current due to temporary grounding of the
PV array.
Corrective measures:
Check the PV system for ground faults (see Section12.3, page80).
3801 to 3805
DC overcurrent > Check generator
Overcurrent at the DC input. The inverter briefly interrupts feed-in operation.
Corrective measures:
If this message is displayed frequently, ensure that the PV array has
been correctly rated and wired.
12 Troubleshooting
SMA Solar Technology AG
Operating Manual 67SB30-50-1AV-40-BE-en-10
67


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for SMA Sunny Boy 5.0 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of SMA Sunny Boy 5.0 in the language / languages: English as an attachment in your email.

The manual is 2,56 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of SMA Sunny Boy 5.0

SMA Sunny Boy 5.0 User Manual - German - 104 pages

SMA Sunny Boy 5.0 User Manual - Dutch - 102 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info