Siemens Building Technologies CE1G3332xx 2015-03-06 3/20
In the supply air duct downstream from the supply air
fan if fan is installed after the last air handling unit,
otherwise
In the supply air duct downstream from the last air
handling unit in a distance of 0.5 m
As a minimum supply air temperature limiter:
In the supply air duct as close as possible to the air dis-
charge into the room
As a dewpoint controller:
Immediately downstream from the droplet separator of
the air washer
Mounting
Procedure:
1. First mount the flange. For drilling holes, refer to “Di-
mensions”.
2. Bend flexible sensing element manually (never use a
tool) so that – when mounted – it stretches diagonally
across the air duct .
Note! The flexible sensing element may not touch the
duct wall: The minimum clearance is 50 mm and the
smallest permissible bending radius 10 mm
3332Z03
3. Fit mounting flange.
4. Slide controller on mounting flange and snap it on.
Electrical installation
Ensure that the local regulations for electrical installa-
tions are complied with
The connecting terminals are located under the flexible
plastic cover
Make wiring according to the plant documentation. If not
available, use the connection diagrams contained in
these Installation Instructions
Observe the permissible cable lengths
Switch on power only when commissioning the controller
External preliminary protection with max. C 10 A circuit
breaker is required in all cases
Settings
1
6
23 5
3332P02
4
1 LED for test mode / normal operation
2 DIP switch block
3 Setting slider for setpoint increase or decrease
4 Setting potentiometer for the relay Q13–Q14
5 Setting potentiometer for the P-band
5 Temperature setting slider for setpoint or limit value
Operating action:
Where? What?
DIP switch block,
switches no. 1 and 2
1 2
Heating and cooling in sequence
Two-stage heating
Single-stage cooling
Single-stage heating
Control mode and integral action time:
DIP switch block,
switches no. 3 and 4
3 4
P-mode
PI mode, integral action time = 600 s
(SLOW)
PI mode, integral action time = 120 s
(FAST)
PI mode, integral action time = 180 s
(MEDIUM)
Test mode:
DIP switch block,
switch no. 5
5
Test mode
Normal operation
Outside temperature compensation:
DIP switch block,
switch no. 6
6
HIGH
LOW
Switching contact Q13–Q14:
Potentiometer 4 Potentiometer setting should correspond to the re-
quired switching point of output relay Q13–Q14
P-band Y1 (not adjustable for Y2):
Potentiometer 5 Potentiometer setting should correspond to the re-
quired range of the controller’s output signal
Setpoint increase / decrease:
Slider 3
Setpoint or limit value (supply or extract air temp.):
Temperature setting
slider 6
Adjust after commissioning
Indication of operating state
The red LED indicates the controller’s operating state:
LED lit: Mains voltage present
LED flashes: In test mode
The LED is also visible when the cover is fitted.
Commissioning
When used as a controller
1. Remove housing cover.
2. Lift flexible plastic cover so that you can access the
setting elements.
3. Make the settings:
Operating action (DIP switches 1 and 2)
Control mode and (with PI mode) integral action
time (DIP switches 3 and 4)
3


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens RLM162 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens RLM162 in the language / languages: English, German, Dutch, Danish, French, Italian, Polish, Swedish, Spanish as an attachment in your email.

The manual is 0,3 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info